{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"FX2N-32ET","brand":"Mitsubishi Electric","brandSlug":"mitsubishi","productSlug":"FX2N-32ET","canonicalUrl":"https://aoctrl.com/mitsubishi/FX2N-32ET","factsUrl":"https://aoctrl.com/api/mcp/products/FX2N-32ET","rawCanonicalId":null},"summary":{"shortDescription":"Mitsubishi FX2N-32ET PLC I/O module, 16-point sink input, 16-point transistor sink output, 30 W, 0.65 kg.","salesMarkdown":"## Grounding and wiring notes Class D grounding with 100 Ω or less is non-negotiable — the module lists it as a requirement. Dedicated ground or common-ground with the rest of the PLC system. Inputs are sink (NPN), no-voltage contact or open collector, 5 mA at 24 VDC ±10%. Outputs are transistor sink, 200 mA per point, 0.2 ms response. Use a M3 screw terminal on removable blocks. Fuse the power supply side with a 250 V 3.15 A rated fuse. Operating temp 0–55 °C, so keep it out of direct sunlight and away from heaters.","metaTitle":"Mitsubishi FX2N-32ET PLC I/O Module, 16/16 Transistor","metaDescription":"Obsolete (EOL) Mitsubishi FX2N-32ET PLC module with 16 sink inputs and 16 transistor outputs. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Mass":"0.65 Kg","Ground":"Class D grounding (grounding resistance: 100 Ω or less)Grounding should be dedicated ground or common ground.","Frequency":"57 to 150 Hz : Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2","ON voltage":"1.5V or less","ON → OFF":"0.2 ms or less / 200 mA (24 VDC)","Input format":"sink","Manufacturer":"Mitsubishi Electric","Use altitude":"Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.","Rated voltage":"AC 100 V to 240 V","Inductive load":"12 W / DC 24 V","Inrush current":"AC 100 V: maximum 40 A 5 ms or less AC 200 V: maximum 60 A 5 ms or less","Noise immunity":"Noise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise si","Use atmosphere":"There is no corrosive property, flammable gas, conductive dust (dust) is not serious","Input impedance":"4.3 kΩ","Rated frequency":"50/60 Hz","Shipping Weight":"1.7 Kg","lifecycle_stage":"eol_hot","Impact resistance":"147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2","Power Consumption":"30 W","Power supply fuse":"250 V 3.15 A (3A)","Relative humidity":"5 to 95% RH (noncondensing).... in operation","Withstand voltage":"Between the power supply terminal (AC power supply) and the earth terminal: AC 1500 V for 1 minute 24 VDC Service power supply and between the input terminal (24 VDC) and the earth terminal: 500 VAC for 1 minute Between the output terminal (transistor)","Circuit insulation":"Photocoupler insulation","Ambient temperature":"0 to 55 ° C. ... Operating -25 to 75 ° C. ..... Save","Estimated Lead Time":"Usually ships in 1 - 10 working days.","Input response time":"About 10 ms","Input signal format":"No-voltage contact input or NPN open collector transistor","Input signal current":"5 mA / 24 VDC","Input signal voltage":"DC 24 V ± 10%","Output type / format":"Transistor / sink output","Application sequencer":"FX1N, FX3G, FX2N, FX3U","External power supply":"DC 5V to 30V","Insulation resistance":"Between each terminal and earth terminal: 500 MV DC 500 MΩ or more with an insulation resistance meter","Input connection shape":"Removable terminal block (M3 screw)","Number of input points":"16 points","Input operation display":"LED on the panel when input is ON","Number of output points":"16 points","Output connection shape":"Removable terminal block (M3 screw)","Voltage tolerance range":"AC 85V ~ 264V","Input circuit insulation":"Photocoupler insulation","Response time OFF → ON":"0.2 ms or less / 200 mA (24 VDC)","24 VDC service power supply":"24 VDC 250 mA or less When input / output expansion block is connected, 24 VDC service power is consumed.","Maximum load Resistive load":"The total load current per 0.5 A / point common should be as follows. . Output 8 points / common: 1.6 A or less","Output operation indication":"LED on the panel when driving the photo coupler","Input ON sensitivity current":"3.5 mA or more","Open-circuit leakage current":"0.1 mA or less / DC 30 V","Direct installation Frequency":"10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2","Input OFF sensitivity current":"1.5 mA or less","Anti-vibration When DIN rail is installed Frequency":"10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$210.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5fafc22d2ad43e43db792f78678458e5.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/FX2N-32ET/alternatives.json"},"ai":{"faq":[{"question":"What's the closest functional second-source for FX2N-32ET?","answer":"Neither the FX5-80SSC-S nor the FX2N-20GM are direct replacements. The FX5-80SSC-S is a safety CPU for iQ-F series; the FX2N-20GM is a motion controller. Both are different products. For a drop-in, you'd need another FX2N series I/O module like the FX2N-32MT (but that's not listed as a peer in our data)."},{"question":"What's the weight of FX2N-32ET?","answer":"Listed mass is 0.65 kg. Shipping weight is 1.7 kg, which includes packaging."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/mitsubishi/FX2N-32ET","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/mitsubishi/FX2N-32ET when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}