{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"FX2N-48ET","brand":"Mitsubishi Electric","brandSlug":"mitsubishi","productSlug":"FX2N-48ET","canonicalUrl":"https://aoctrl.com/mitsubishi/FX2N-48ET","factsUrl":"https://aoctrl.com/api/mcp/products/FX2N-48ET","rawCanonicalId":null},"summary":{"shortDescription":"Mitsubishi FX2N-48ET – PLC I/O module, 24 inputs / 24 outputs, transistor sink, removable terminal blocks, 0.85 kg.","salesMarkdown":"Mitsubishi FX2N-48ET: 24 sink inputs and 24 transistor sink outputs on removable M3 screw terminal blocks. Requires Class D grounding (100 Ω or less) and AC 100–240 V, 50/60 Hz, 35 W supply. ## Wiring & Grounding Notes Input wiring: NPN open collector or no-voltage contact, 24 VDC ±10%, 5 mA per point, response time ~10 ms. Output wiring: transistor (sink), rated 200 mA per channel, ON→OFF and OFF→ON both ≤0.2 ms at 200 mA, 24 VDC. Use the removable terminal block (M3 screw) for panel-side harnesses. Ground the module via a dedicated Class D circuit (≤100 Ω); shared grounding may inject noise from power equipment. The supply side requires a 5 A 250 V fuse on the AC line. Ambient temperature must stay within 0–55 °C operating, with non-condensing humidity 5–95%.","metaTitle":"Mitsubishi FX2N-48ET PLC I/O, 24/24 Transistor Sink, Obsolet","metaDescription":"FX2N-48ET is end-of-life. 24 inputs/24 outputs transistor/sink output on removable terminal blocks. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Mass":"0.85 Kg","Ground":"Class D grounding (grounding resistance: 100 Ω or less)Grounding should be dedicated ground or common ground.","Frequency":"57 to 150 Hz : Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2","ON voltage":"1.5V or less","ON → OFF":"0.2 ms or less / 200 mA (24 VDC)","Input format":"sink","Manufacturer":"Mitsubishi Electric","Use altitude":"Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.","Rated voltage":"AC 100 V to 240 V","Inductive load":"12 W / DC 24 V","Inrush current":"AC 100 V: maximum 40 A 5 ms or less AC 200 V: maximum 60 A 5 ms or less","Noise immunity":"Noise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise si","Use atmosphere":"There is no corrosive property, flammable gas, conductive dust (dust) is not serious","Input impedance":"4.3 kΩ","Rated frequency":"50/60 Hz","Shipping Weight":"1.9 Kg","lifecycle_stage":"eol_hot","Impact resistance":"147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2","Power Consumption":"35W","Power supply fuse":"250 V 5 A","Relative humidity":"5 to 95% RH (noncondensing).... in operation","Withstand voltage":"Between the power supply terminal (AC power supply) and the earth terminal: AC 1500 V for 1 minute 24 VDC Service power supply and between the input terminal (24 VDC) and the earth terminal: 500 VAC for 1 minute Between the output terminal (transistor)","Circuit insulation":"Photocoupler insulation","Ambient temperature":"0 to 55 ° C. ... Operating -25 to 75 ° C. ..... Save","Estimated Lead Time":"Usually ships in 1 - 10 working days.","Input response time":"About 10 ms","Input signal format":"No-voltage contact input or NPN open collector transistor","Input signal current":"5 mA / 24 VDC","Input signal voltage":"DC 24 V ± 10%","Output type / format":"Transistor / sink output","Application sequencer":"FX1N, FX3G, FX2N, FX3U","External power supply":"DC 5V to 30V","Insulation resistance":"Between each terminal and earth terminal: 500 MV DC 500 MΩ or more with an insulation resistance meter","Input connection shape":"Removable terminal block (M3 screw)","Number of input points":"24 points","Input operation display":"LED on the panel when input is ON","Number of output points":"24 points","Output connection shape":"Removable terminal block (M3 screw)","Voltage tolerance range":"AC 85V ~ 264V","Input circuit insulation":"Photocoupler insulation","Response time OFF → ON":"0.2 ms or less / 200 mA (24 VDC)","24 VDC service power supply":"24 VDC 460 mA or less When connecting input / output extension block, 24 VDC service power is consumed.","Maximum load Resistive load":"The total load current per 0.5 A / point common should be as follows. . Output 4 points / common: 0.8 A or less . Output 8 points / common: 1.6 A or less","Output operation indication":"LED on the panel when driving the photo coupler","Input ON sensitivity current":"3.5 mA or more","Open-circuit leakage current":"0.1 mA or less / DC 30 V","Direct installation Frequency":"10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2","Input OFF sensitivity current":"1.5 mA or less","Anti-vibration When DIN rail is installed Frequency":"10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$392.00","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/FX2N-48ET/alternatives.json"},"ai":{"faq":[{"question":"What grounding is required for the FX2N-48ET?","answer":"Class D grounding with a resistance of 100 Ω or less; dedicated or common ground is acceptable."},{"question":"Will the FX2N-48ET drop into a panel wired for the FX2N-32ER-ES/UL?","answer":"No. The FX2N-48ET uses transistor sink outputs (24 points) instead of relay outputs, and has a different I/O count (24 inputs/24 outputs vs 16/16). Wiring must change at the terminal block."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/mitsubishi/FX2N-48ET","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/mitsubishi/FX2N-48ET when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}