{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"FX2N-8ER","brand":"Mitsubishi Electric","brandSlug":"mitsubishi","productSlug":"FX2N-8ER","canonicalUrl":"https://aoctrl.com/mitsubishi/FX2N-8ER","factsUrl":"https://aoctrl.com/api/mcp/products/FX2N-8ER","rawCanonicalId":null},"summary":{"shortDescription":"Mitsubishi FX2N-8ER expansion I/O module, 4 DC sink inputs (24 VDC, 4.3 kΩ) and 4 relay outputs (2 A per point), 0.2 kg, end-of-life.","salesMarkdown":"4 DC inputs on the FX2N-8ER expect a sink (NPN) signal at 24 VDC, with 4.3 kΩ impedance drawing 5 mA per point. Relay outputs handle 2 A resistive per point, 8 A per four-point common. Response time is about 10 ms ON-to-OFF. Powered from the PLC backplane; no external supply needed. ## Integration Ambient operating temperature 0 to 55 °C, storage -25 to 75 °C. Rated vibration per IEC 61131-2: 0.075 mm amplitude at 10-57 Hz, 9.8 m/s² at 57-150 Hz. Use altitude limited to 2000 m or less.","metaTitle":"Mitsubishi FX2N-8ER Expansion I/O, 4DI/4DO Relay, EOL","metaDescription":"Mitsubishi FX2N-8ER expansion I/O module: 4 DC sink inputs (24 V, 4.3 kΩ), 4 relay outputs (2 A/point, 8 A/common). End-of-life (eol_hot). Sourced to order against RFQ. 0.2 kg.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Mass":"0.2 Kg","Frequency":"57 to 150 Hz : Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2","ON → OFF":"About 10 ms","Input format":"sink","Manufacturer":"Mitsubishi Electric","Minimum load":"DC 5 V 2 mA (reference value)","Use altitude":"Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.","Rated voltage":"Internal power supply from the sequencer","Inductive load":"80VA","Noise immunity":"Noise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise si","Use atmosphere":"There is no corrosive property, flammable gas, conductive dust (dust) is not serious","Input impedance":"4.3 kΩ","Shipping Weight":"1.2 Kg","lifecycle_stage":"eol_hot","Impact resistance":"147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2","Relative humidity":"5 to 95% RH (noncondensing).... in operation","Withstand voltage":"Between the input terminal (24 VDC) and the earth terminal: 500 V AC for 1 min Between the output terminal (relay) and the earth terminal: AC 1500 V 1 min","Circuit insulation":"Mechanical insulation","Ambient temperature":"0 to 55 ° C. ... Operating -25 to 75 ° C. ..... Save","Estimated Lead Time":"Usually ships in 1 - 10 working days.","Input response time":"About 10 ms","Input signal format":"No-voltage contact input NPN or open collector transistor","Input signal current":"5 mA / 24 VDC","Input signal voltage":"DC 24 V ± 10%","Output type / format":"relay","Application sequencer":"FX1N, FX3G, FX2N, FX3U, FX1NC, FX3GC, FX2NC, FX3UCFX2NC - CNV - IF is required for connection to FX1NC and FX2NC. To connect to FX3GC, FX3UC, FX2NC - CNV - IF or FX3UC - 1PS - 5V is required.","External power supply":"DC 30 V or less AC 240 V or less","Insulation resistance":"Between each terminal and earth terminal: 500 MV DC 500 MΩ or more with an insulation resistance meter","Input connection shape":"Vertical terminal block (M3 screw)","Number of input points":"4 points","Input operation display":"LED on the panel when input is ON","Number of output points":"4 points","Output connection shape":"Vertical terminal block (M3 screw)","Input circuit insulation":"Photocoupler insulation","Response time OFF → ON":"About 10 ms","Maximum load Resistive load":"Total load current of 2A / 1 point common per resistance load should be as follows. Output 4 points / common: 8 A or less","Output operation indication":"When the relay coil is energized LED on the panel is lit","Input ON sensitivity current":"3.5 mA or more","Direct installation Frequency":"10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2","Input OFF sensitivity current":"1.5 mA or less","Anti-vibration When DIN rail is installed Frequency":"10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$84.00","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/FX2N-8ER/alternatives.json"},"ai":{"faq":[{"question":"What are the key specifications?","answer":"4 DC sink inputs at 24 VDC, 4.3 kΩ impedance, 5 mA per point. 4 relay outputs rated 2 A resistive per point, 8 A per common. Response time approximately 10 ms. Mass 0.2 kg."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/mitsubishi/FX2N-8ER","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/mitsubishi/FX2N-8ER when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}