{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"G9SX-EX401-RC","brand":"Omron","brandSlug":"omron","productSlug":"G9SX-EX401-RC","canonicalUrl":"https://aoctrl.com/omron/G9SX-EX401-RC","factsUrl":"https://aoctrl.com/api/mcp/products/G9SX-EX401-RC","rawCanonicalId":null},"summary":{"shortDescription":"Omron G9SX-EX401-RC Flexible Safety Unit, expansion type, 24 VDC, 4 safety outputs + 1 auxiliary, spring-cage terminals.","salesMarkdown":"The Omron G9SX-EX401-RC is a Flexible Safety Unit configured as an expansion module, adding 4 instantaneous safety outputs and 1 auxiliary output to a G9SX safety system. It runs on a 24 VDC supply with a ±15% tolerance and draws 2 W max. Contact ratings are 250 VAC, 3 A or 30 VDC, 3 A for resistive loads, with a maximum switching voltage of 250 VAC / 125 VDC. Rated carry current is 3 A. Response time from ON to OFF is 10 ms max; OFF to ON is 30 ms max. No OFF-delay function is built in. Durability is specified at 100,000 electrical cycles minimum at rated load (1,800 cycles/hour) and 5,000,000 mechanical cycles minimum (7,200 cycles/hour). Vibration resistance covers 10 to 55 Hz at 0.375 mm single amplitude.","metaTitle":"Omron G9SX-EX401-RC Flexible Safety Unit, 24 VDC, 4 safety o","metaDescription":"Omron G9SX-EX401-RC Flexible Safety Unit expansion with 4 safety outputs, 1 auxiliary. Rated 250 VAC/30 VDC 3A resistive. 24 VDC supply. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Safety Relays"],"specifications":{"title":"G9SX-EX401-RC","Weight":"0.165 kg","Durability":"Electrical: 100,000 cycles min. (rated load, switching frequency: 1,800 cycles/hour)Mechanical: 5,000,000 cycles min. (switching frequency: 7,200 cycles/hour)","Electrical":"100,000 cycles min. (rated load, switching frequency: 1,800 cycles/hour)","Mechanical":"5,000,000 cycles min. (switching frequency: 7,200 cycles/hour)","Rated load":"250 VAC, 3A/30 VDC, 3A (resistive load)","description":"Flexible Safety Unit","Product Type":"Flexible Safety Unit","EX - Functions":"Expansion Unit","Product Number":"G9SX-EX401-RC","Shipping Weight":"1.5 kg","lifecycle_stage":"current","Estimated Lead Time":"1 - 10 Working days","Rated carry current":"3 A","Rated supply voltage":"24 VDC","Vibration resistance":"Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)","Operating voltage range":"−15% to 10% of rated supply voltage","Rated power consumption":"2 W max.","RC - Terminal Block Type":"Spring-cage terminals","Maximum switching voltage":"250 VAC, 125 VDC","Response time (ON to OFF state)":"10 ms max.","Operating time (OFF to ON state)":"30 ms max.","No indicator - Max. OFF-delay Time":"No OFF delay","1 - Output Configuration (Auxiliary Outputs)":"1 output","4 - Output Configuration (Instantaneous Safety Outputs)":"4 outputs"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/270858447b217f7a74fd4443c6c437b8.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What are the key ratings for the G9SX-EX401-RC?","answer":"It is a 24 VDC expansion safety unit with 4 safety outputs and 1 auxiliary output, rated 250 VAC/30 VDC 3 A resistive load. Electrical durability is 100,000 cycles minimum; mechanical durability is 5,000,000 cycles minimum."},{"question":"What type of terminals does the G9SX-EX401-RC use?","answer":"It uses spring-cage terminals (RC type), which accept solid or ferruled stranded wire without tools."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/omron/G9SX-EX401-RC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/omron/G9SX-EX401-RC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}