{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GC1622F6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GC1622F6","canonicalUrl":"https://aoctrl.com/schneider/GC1622F6","factsUrl":"https://aoctrl.com/api/mcp/products/GC1622F6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GC modular contactor, GC1622F6, 4P, 110 V AC 60 Hz control, 16 A, clip-on DIN rail, 2 x 18 mm modules.","salesMarkdown":"It is a 4-pole (4P) device rated for AC-7A and AC-7B utilisation categories, meaning it handles both resistive and lightly inductive loads — typical for contactor-duty applications like fan coils, pumps under 1 kW, and resistive heating banks. The control circuit is 110 V AC at 60 Hz, with a drop-out range of 0.2...0.75 Uc and an operating range of 0.85...1.1 Uc at 50 Hz. The continuous thermal current (Ith) is 16 A at 50 Hz for the power circuit, with an average impedance of 2.5 mOhm, so the contactor is sized for a 16 A feeder. The associated fuse rating is 16 A gL at ≤ 440 V for the power circuit, which coordinates with the contactor's short-circuit withstand. Mechanical durability is 1,000,000 cycles; electrical durability is 100,000 cycles for both AC-7A and AC-7B duty — this is the wear life under rated load, not the mechanical cycle count. Clip-on mounting on standard DIN rail (35 mm per EN 60715). The contactor occupies 2 modules of 18 mm width each (36 mm total), so it fits a standard 18 mm pitch DIN-rail terminal block layout. Height is 85 mm, depth 62.5 mm — shallow enough for most 100 mm deep enclosures. Screw-clamp terminals on both control and power circuits: control accepts up to 2 x 2.5 mm² flexible without cable end; power accepts up to 2 x 6 mm² flexible without cable end. Tightening torque is 0.8 N.m for both circuits. IP20 protection (in enclosure per VDE 0106) means it is not sealed against dust ingress — install in a panel with at least IP40 enclosure.","metaTitle":"TeSys GC1622F6 modular contactor, 110 V AC 60 Hz, 4P, DIN ra","metaDescription":"Schneider Electric TeSys GC1622F6 modular contactor, 4P, 110 V AC 60 Hz control, AC-7A/AC-7B, 16 A, clip-on DIN rail, IEC 60947-5 & IEC 61095. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"62.5 mm","Width":"36 mm","Height":"85 mm","Current":"16 A AC-7 A 5 A AC-7B","Voltage":"<= 250 V AC","Application":"Heating Lighting Motor control","Coil Voltage":"110 V AC 60 Hz","Control Type":"Remote control","Operating Time":"10...25 ms opening 10...30 ms closing","Product Status":"Active","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V conforming to IEC 61095 500 V conforming to VDE 0110","Operating Position":"30°/vertical","Temp Operating Max":"50 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...70 °C","Control Circuit Type":"AC at 60 Hz","Utilization Category":"AC-7 A AC-7B","Electrical Life Cycles":"AC-7 A: 100000 cycles AC-7B: 100000 cycles","Mechanical Life Cycles":"1000000 cycles","Main Product Or Component Type":"Modular contactor","Ambient Air Temperature Operation":"-5...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c5640e0088f1e0b14feff3c1a3d3288a.pdf","sourceUrl":"https://www.se.com/uk/en/product/GC1622F6/tesys-gc-modular-contactor-16-a-2-no-+-2-nc-coil-110-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GC1622F6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GC1622F6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GC1622F6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}