{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GS2VG4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GS2VG4","canonicalUrl":"https://aoctrl.com/schneider/GS2VG4","factsUrl":"https://aoctrl.com/api/mcp/products/GS2VG4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GS, switch-disconnector-fuse, 4 poles, 1250 A thermal, DIN 4, 560 kW at 400 V.","salesMarkdown":"It carries a conventional free air thermal current of 1250 A at 40 °C, with an operational current of 1000 A at 440 V in AC-23B duty — the heavy motor-switching category per IEC 60947-3. Rated operational power reaches 560 kW at 400 V and 475 kW at 690 V. Breaking capacity is 8000 A at 400 V (AC-23B), and making capacity hits 10000 A at 400 V AC-23B — meaning it can close onto a fault of that magnitude without welding contacts. Short-circuit withstand is 90 kA, so it coordinates with upstream protective devices in a high-fault panel. Plate-mounted, with an external left-side operating handle. The DIN 4 fuse size means it accepts standard DIN-style fuse links. Power connections accept bars up to 80 mm² or ring terminals on up to 4 cables of 185 mm² each — sized for the 1250 A feed. Tightening torque on the power circuit is 44 N·m, so a torque wrench is part of the install kit. The body and fuse cover are rated for 960 °C and 850 °C glow-wire resistance respectively, per IEC 60695-2-1. This part is classified as obsolete by the manufacturer.","metaTitle":"Schneider TeSys GS2VG4 Switch-Disconnector-Fuse, 1250A, 4P,","metaDescription":"Obsolete TeSys GS2VG4 switch-disconnector-fuse. 1250A thermal, 1000A AC-23B at 440V, 560 kW at 400V. IEC 60947-3. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"289 mm","Range":"TeSys","Width":"562 mm","Height":"355 mm","Fuse size":"4","Fuse type":"DIN","Standards":"IEC 60947-3","Network type":"DC AC","Product name":"TeSys GS","Fire resistance":"850 °C fuse cover conforming to IEC 60695-2-1 960 °C body conforming to IEC 60695-2-1","Making capacity":"10000 A at 400 V AC-23B","lifecycle_stage":"current","Mounting support":"Plate","Breaking Capacity":"110 W","Breaking capacity":"8000 A at 400 V (AC-23B)","Device short name":"GS2V","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"Power circuit: 44 N.m","Electrical durability":"100 cycles DC-23A 100 cycles DC-23B 500 cycles AC-23A 500 cycles AC-23B","Mechanical durability":"5000 cycles","Connections - terminals":"Power circuit: bars80 mm² Power circuit: lugs-ring terminals 4 cable(s) 185 mm²","IP degree of protection":"IP20 conforming to IEC 60529 (with terminal cover)","Short-circuit withstand":"90 kA","Type of operating handle":"External left side","Product or component type":"Switch-disconnector-fuse","Protected poles description":"4t","Rated operational power in W":"400 kW at 690 V 475 kW at 690 V 560 kW at 400 V 560 kW at 500 V","Contacts type and composition":"4 NO","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz","[Ie] rated operational current":"1000 A at 440 V 2 poles in series per phase DC-23A 1000 A at 440 V 2 poles in series per phase DC-23B 630 A at 690 V AC-23A 630 A at 690 V AC-23B 1000 A at 440 V AC-23A 1000 A at 440 V AC-23B 800 A at 500 V AC-23A 800 A at 500 V AC-23B","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-20...70 °C","[Uimp] rated impulse withstand voltage":"12 kV","[Icm] rated short-circuit making capacity":"80 kA at 400 V with protection by gG fuses","[Ith] conventional free air thermal current":"1250 A (at 40 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/GS2VG4/tesys-gs-switchdisconnectorfuse-4-p-1250a-din-4/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GS2VG4/alternatives.json"},"ai":{"faq":[{"question":"What is the closest replacement for GS2VG4?","answer":"No official successor order code is published. For a new design, look at the current TeSys GS or TeSys GV7 ranges, matching the DIN 4 fuse size and 4-pole configuration."},{"question":"What are the key ratings for GS2VG4?","answer":"1250 A conventional free air thermal current (Ith), 1000 A at 440 V AC-23B operational current, 560 kW at 400 V, breaking capacity 8000 A at 400 V AC-23B, making capacity 10000 A at 400 V AC-23B, short-circuit withstand 90 kA."},{"question":"What standards does GS2VG4 comply with?","answer":"IEC 60947-3 for switch-disconnectors. The fuse cover meets 850 °C glow-wire (IEC 60695-2-1) and the body meets 960 °C. IP20 with terminal cover per IEC 60529."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GS2VG4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GS2VG4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}