{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2DM102BL","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2DM102BL","canonicalUrl":"https://aoctrl.com/schneider/GV2DM102BL","factsUrl":"https://aoctrl.com/api/mcp/products/GV2DM102BL","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2DM102BL, DOL non-reversing motor starter, 0.16…0.25 A thermal protection, 24 V DC control, 3-pole, 50 kA breaking capacity at 400 V.","salesMarkdown":"The Schneider Electric GV2DM102BL is a TeSys Deca direct-on-line (DOL) motor starter — a pre-assembled combination of a GV2ME motor circuit breaker, an LC1D contactor, and a GV2AF3 combination block in one 3-pole non-reversing package. It is built for small motor loads: the thermal protection adjustment range of 0.16…0.25 A and motor power rating of 0.06 kW at 400…415 V AC tell you this is sized for fractional-horsepower motors — think small fans, dosing pumps, or conveyor sections drawing under a quarter amp. The 24 V DC control circuit voltage is common for PLC-driven panels; the coil holds at 24 VDC nominal, so verify your DC supply stays within tolerance. The magnetic tripping current is set at 2.4 A — this is the instantaneous short-circuit trip threshold, not the thermal overload setting. That means the breaker element clears a fault magnetically at roughly 10× the top of the thermal adjustment band, giving fast response on a hard short while letting the thermal bimetal handle sustained overloads. Coordination types 1 and 2 are both supported, so you can select the degree of damage acceptance on downstream contactors during a fault. The GV2DM102BL occupies a 45 mm wide footprint on the DIN rail — a single modular pitch. Depth is 99.6 mm, height 176.4 mm. The device composition is a factory-matched assembly of three components (breaker, contactor, combination block), so there is no separate wiring between them inside the package; power terminals for line and load are the only connections needed, plus the 24 VDC control wires to the contactor coil.","metaTitle":"Schneider Electric GV2DM102BL TeSys Deca Motor Starter, 0.16","metaDescription":"Schneider Electric GV2DM102BL DOL motor starter, TeSys Deca series, 0.16-0.25 A thermal range, 24 VDC coil, 50 kA breaking capacity. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"99.6 mm","Width":"45 mm","Height":"176.4 mm","Motor power kW":"0.06 kW at 400...415 V AC 50/60 Hz 0.06 kW at 440 V AC 50/60 Hz","lifecycle_stage":"current","Range of product":"TeSys Deca","Coordination type":"Type 1 Type 2","Device short name":"GV2DM","Poles description":"3P","Device composition":"1 3-pole contactor LC1D 1 motor circuit breaker type GV2ME 1 combination block GV2AF3","Motor starter type":"Non reversing","Utilisation category":"AC-3","Rated breaking capacity":"Iq 50 kA at 400...415 V conforming to IEC 60947-4-1 Iq 50 kA at 440 V conforming to IEC 60947-4-1 Iq 50 kA at 500 V conforming to IEC 60947-4-1","Magnetic tripping current":"2.4 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"24 V DC","Thermal protection adjustment range":"0.16...0.25 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/833641c3fe8988864268f0510edd59d3.pdf","sourceUrl":"https://www.se.com/uk/en/product/GV2DM102BL/dol-combination-starter-tesys-deca-0-16-0-25-a-24-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2DM102BL/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the GV2DM102BL?","answer":"The GV2DM102BL has a rated breaking capacity (Iq) of 50 kA at 400…415 V, 440 V, and 500 V, conforming to IEC 60947-4-1. This is high for a starter in this amp range and means it can handle severe fault currents without upstream damage."},{"question":"Where can I buy the GV2DM102BL?","answer":"The GV2DM102BL is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quotation — submit an RFQ to check lead time and price."},{"question":"What thermal protection range does the GV2DM102BL cover?","answer":"The thermal protection adjustment range is 0.16…0.25 A. This sets the overload trip point for the motor circuit breaker element. The magnetic instantaneous trip is fixed at 2.4 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2DM102BL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2DM102BL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}