{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2DM104V7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2DM104V7","canonicalUrl":"https://aoctrl.com/schneider/GV2DM104V7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2DM104V7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2DM104V7, DOL combination motor starter, 0.4…0.63 A thermal adjustment, 400 V AC, 3-pole, Type 1 coordination.","salesMarkdown":"Its thermal protection adjustment range of 0.4…0.63 A sets the overload trip point for the connected motor — set the dial to the motor's full-load current, not the nameplate service factor. Rated for AC-3 utilisation category, it handles the high inrush of squirrel-cage induction motors during starting. Rated breaking capacity Iq of 50 kA at 400/415 V and 440 V, per IEC 60947-4-1. Coordination is Type 1, so after a short-circuit the starter may need contact replacement, but the downstream motor and cable remain protected. ## Motor power and magnetic trip Motor power rating reaches 0.18 kW at 400/415 V and 440 V AC, 50/60 Hz. The magnetic tripping current is fixed at 8 A — this is the instantaneous magnetic release that clears short-circuits; it does not adjust with the thermal dial. For a motor drawing 0.4…0.63 A full-load, the 8 A magnetic trip provides a healthy margin against nuisance trips during starting inrush. Width of 45 mm matches the standard 45 mm per-pole pitch on DIN-rail or panel-mount layouts. Depth of 99.6 mm and height of 176.4 mm — verify clearance inside the enclosure door before wiring, especially if a right-angle gland plate or busbar shroud is present. The non-reversing configuration keeps the contactor block compact; reversing applications need a separate GV2DR variant.","metaTitle":"TeSys Deca GV2DM104V7 Motor Starter, 0.4…0.63 A, 400 V AC","metaDescription":"Schneider Electric TeSys Deca GV2DM104V7 DOL combination starter, 0.4…0.63 A thermal range, 50 kA breaking capacity at 400 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"99.6 mm","Width":"45 mm","Height":"176.4 mm","Motor power kW":"0.12 kW at 400/415 V AC 50/60 Hz 0.18 kW at 400/415 V AC 50/60 Hz 0.18 kW at 440 V AC 50/60 Hz","lifecycle_stage":"current","Range of product":"TeSys Deca","Coordination type":"Type 1","Device short name":"GV2DM","Poles description":"3P","Device composition":"1 3-pole contactor 1 motor circuit breaker type GV2ME 1 combination block GV2AF3","Motor starter type":"Non reversing","Utilisation category":"AC-3","Rated breaking capacity":"Iq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 50 kA at 440 V conforming to IEC 60947-4-1 Iq 50 kA at 500 V conforming to IEC 60947-4-1","Magnetic tripping current":"8 A","Product or component type":"Motor starter","Thermal protection adjustment range":"0.4...0.63 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6dd585f28be79bb597e0f41c84e223bc.pdf","sourceUrl":"https://www.se.com/uk/en/product/GV2DM104V7/dol-combination-starter-tesys-deca-0-4-0-63-a-400v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2DM104V7/alternatives.json"},"ai":{"faq":[{"question":"What is the thermal protection adjustment range on this starter?","answer":"The thermal protection adjustment range is 0.4…0.63 A. Set the dial to match the motor's full-load amperage — the magnetic trip is fixed at 8 A and does not change with the dial setting."},{"question":"What breaking capacity does the GV2DM104V7 offer at 400 V?","answer":"Rated breaking capacity Iq is 50 kA at 400/415 V and 440 V, conforming to IEC 60947-4-1. Coordination is Type 1, meaning the starter may need contact inspection after a fault but the motor and cable are protected."},{"question":"Where can I buy the GV2DM104V7 and how is it quoted?","answer":"The GV2DM104V7 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock or price figures are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2DM104V7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2DM104V7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}