{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2DM107P7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2DM107P7","canonicalUrl":"https://aoctrl.com/schneider/GV2DM107P7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2DM107P7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2DM107P7, DOL combination motor starter, 1.6...2.5 A thermal protection, 230 V AC 50/60 Hz coil, 3-pole, non-reversing.","salesMarkdown":"It integrates a GV2ME motor circuit breaker, a 3-pole contactor, and a GV2AF3 combination block into a single, pre-assembled unit for non-reversing motor control. The thermal protection adjustment range is 1.6...2.5 A, and the magnetic trip is fixed at 33.5 A. Rated breaking capacity is 50 kA at 400/415 V, 440 V, and 500 V, conforming to IEC 60947-4-1 for Type 1 coordination. Its footprint is 45 mm wide, 176.4 mm tall, and 99.6 mm deep — a compact 3-pole block that fits a standard motor control center bucket or panel enclosure. It is a DOL combination starter, so it handles the motor circuit breaker, contactor, and control wiring in one assembly. For a commissioning engineer, this means fewer interconnections to wire and test compared to a separate breaker-and-contactor build.","metaTitle":"Schneider GV2DM107P7 TeSys Deca Motor Starter, 1.6-2.5A","metaDescription":"Obsolete GV2DM107P7 TeSys Deca DOL motor starter, 1.6-2.5A thermal range, 230V AC coil, 50 kA breaking capacity. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"99.6 mm","Width":"45 mm","Height":"176.4 mm","Motor power kW":"0.75 kW at 400/415 V AC 50/60 Hz 0.75 kW at 440 V AC 50/60 Hz 1.1 kW at 440 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Range of product":"TeSys Deca","Coordination type":"Type 1","Device short name":"GV2DM","Poles description":"3P","Device composition":"1 motor circuit breaker type GV2ME 1 3-pole contactor 1 combination block GV2AF3","Motor starter type":"Non reversing","Utilisation category":"AC-3","Rated breaking capacity":"Iq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 50 kA at 440 V conforming to IEC 60947-4-1 Iq 50 kA at 500 V conforming to IEC 60947-4-1","Magnetic tripping current":"33.5 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"230 V AC 50/60 Hz","Thermal protection adjustment range":"1.6...2.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f86878dfe761e51b17dfb8a41f13e996.pdf","sourceUrl":"https://www.se.com/vn/en/product/GV2DM107P7/dol-combination-starter-tesys-deca-1-6-2-5a-230v-ac-50-60hz-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2DM107P7/alternatives.json"},"ai":{"faq":[{"question":"What replaces the GV2DM107P7?","answer":"The evidence does not list an official successor order code. For a direct replacement, you would need to cross-reference the motor rating (0.75 kW at 400 V) and thermal range (1.6-2.5 A) against the current TeSys Deca or TeSys Island range. The GV2DM107P7 is a non-reversing DOL starter with a 230 V AC coil; any substitute must match these parameters and the Type 1 coordination rating."},{"question":"How do I source the GV2DM107P7 if it is obsolete?","answer":"Through the independent surplus and broker channel. We can source this part to order against an RFQ. Submit a request with the target quantity and price, and we will locate verified inventory from our network."},{"question":"What are the key ratings for the GV2DM107P7?","answer":"Thermal protection adjustment range is 1.6...2.5 A. Magnetic trip is 33.5 A. Control circuit coil is 230 V AC 50/60 Hz. Rated breaking capacity is 50 kA at 400/415 V, 440 V, and 500 V. Motor power is 0.75 kW at 400/415 V and 440 V, and 1.1 kW at 440 V and 500 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2DM107P7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2DM107P7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}