{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2DM120U7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2DM120U7","canonicalUrl":"https://aoctrl.com/schneider/GV2DM120U7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2DM120U7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2DM120U7 DOL combination starter, 13-18 A thermal adjustment, 240 V AC coil, 3-pole non-reversing, Type 1 coordination.","salesMarkdown":"The GV2DM120U7 is a direct-on-line combination starter from the TeSys Deca range — a single assembly that packages a motor circuit breaker (GV2ME type), a 3-pole contactor, and a combination block (GV2AF3) into one DIN-rail footprint. The thermal protection adjustment range is 13 to 18 A, and the magnetic trip is fixed at 223 A. For a 400/415 V AC supply, it handles 7.5 kW motor loads in AC-3 duty; at 440 V AC the rating rises to 9 kW, and at 500 V AC it also delivers 9 kW. The coil is wound for 240 V AC control. ## Coordination and breaking capacity This starter is configured for Type 1 coordination, meaning that after a short-circuit fault up to the rated breaking capacity the starter may need component replacement, but the installation remains safe and the short circuit is cleared. The rated breaking capacity (Iq) is 15 kA at 400/415 V, 8 kA at 440 V, and 6 kA at 500 V, all conforming to IEC 60947-4-1. For a panel builder, Type 1 is the standard choice when downstream damage is acceptable after a fault — it keeps the enclosure size smaller than Type 2 coordination. ## Physical integration The GV2DM120U7 occupies a 45 mm wide DIN-rail footprint, with a depth of 99.6 mm and a height of 176.4 mm. That 45 mm width is the same as a standard TeSys D contactor or GV2 breaker — it fits existing panel layouts without re-spacing. The combination block (GV2AF3) is pre-wired to the contactor and breaker, so the assembly arrives as one unit ready for line and load connections.","metaTitle":"GV2DM120U7 TeSys Deca Motor Starter, 13-18 A, 240 V AC","metaDescription":"GV2DM120U7 DOL combination starter, 13-18 A thermal range, 7.5 kW at 400/415 V AC, AC-3, Type 1 coordination. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"99.6 mm","Width":"45 mm","Height":"176.4 mm","Motor power kW":"7.5 kW at 400/415 V AC 50/60 Hz 9 kW at 440 V AC 50/60 Hz 7.5 kW at 440 V AC 50/60 Hz 9 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Range of product":"TeSys Deca","Coordination type":"Type 1","Device short name":"GV2DM","Poles description":"3P","Device composition":"1 combination block GV2AF3 1 3-pole contactor 1 motor circuit breaker type GV2ME","Motor starter type":"Non reversing","Utilisation category":"AC-3","Rated breaking capacity":"Iq 15 kA at 400/415 V conforming to IEC 60947-4-1 Iq 8 kA at 440 V conforming to IEC 60947-4-1 Iq 6 kA at 500 V conforming to IEC 60947-4-1","Magnetic tripping current":"223 A","Product or component type":"Motor starter","Thermal protection adjustment range":"13...18 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/824662853ac5a6cc27f311255655d063.pdf","sourceUrl":"https://www.se.com/uk/en/product/GV2DM120U7/dol-combination-starter-tesys-deca-13-18-a-240-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2DM120U7/alternatives.json"},"ai":{"faq":[{"question":"What is the thermal adjustment range of GV2DM120U7?","answer":"The thermal protection adjustment range is 13 to 18 A. The magnetic trip is fixed at 223 A."},{"question":"How do I get current pricing and availability for GV2DM120U7?","answer":"The GV2DM120U7 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is GV2DM120U7's rated breaking capacity?","answer":"The rated breaking capacity (Iq) is 15 kA at 400/415 V, 8 kA at 440 V, and 6 kA at 500 V, all conforming to IEC 60947-4-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2DM120U7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2DM120U7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}