{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2LE05","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2LE05","canonicalUrl":"https://aoctrl.com/schneider/GV2LE05","factsUrl":"https://aoctrl.com/api/mcp/products/GV2LE05","rawCanonicalId":null},"summary":{"shortDescription":"Manufacturer: Schneider Electric, Series: TeSys Deca, Type: Motor circuit breaker, Code: GV2LE05, Rated current: 1 A, Breaking capacity: 100 kA, Poles: 3, Mounting: DIN rail","salesMarkdown":"The GV2LE05 3-pole motor circuit breaker from the TeSys Deca range handles motor protection at 1 A line current with a 100 kA breaking capacity at 400 V AC. Its magnetic trip fires at 15.1 A, which covers the inrush of motors from 0.25 to 0.75 kW on 400/415 V supplies. Suitable for isolation per IEC 60947-1. Rated for AC-3 and AC-3e duty cycles, it withstands 100,000 electrical operations at rated current. Power dissipation per pole is 1.8 W. Certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, with fire resistance to 960 °C (IEC 60695-2-11). Screw clamp terminals accept 1–6 mm² solid or 1.5–6 mm² flexible conductors; tighten to 1.7 N·m. The breaker is IP20 finger-safe and meets IK04 impact protection. Withstands 30 Gn shock for 11 ms and 5 Gn vibration over 5–150 Hz.","metaTitle":"Schneider Electric GV2LE05 Motor Circuit Breaker, 1 A, 100 k","metaDescription":"Schneider Electric GV2LE05 TeSys Deca motor circuit breaker. 1 A rated, 100 kA breaking capacity at 400 V AC, 3-pole, magnetic trip 15.1 A, IP20. Active production, certified EN/IE","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"3.09 in (78.5 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US1CP1018402","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate)","Control Type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.25 kW 400/415 V AC 50/60 Hz 0.37 kW 400/415 V AC 50/60 Hz 0.37 kW 500 V AC 50/60 Hz 0.55 kW 690 V AC 50/60 Hz 0.75 kW 690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2LE","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"1 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"15.1 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"1.8 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"1 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$20.32","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c027c092fd35b072e619993e6d0ac0f1.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2LE05/alternatives.json"},"ai":{"faq":[{"question":"What compliance standards does the GV2LE05 meet?","answer":"It is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-2-40 Annex JJ, plus IEC 60695-2-11 fire resistance at 960 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2LE05","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2LE05 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}