{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2LE08","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2LE08","canonicalUrl":"https://aoctrl.com/schneider/GV2LE08","factsUrl":"https://aoctrl.com/api/mcp/products/GV2LE08","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2 motor circuit breaker, GV2LE08, 4 A rated current, 3 poles, dark grey.","salesMarkdown":"## GV2LE08 – Motor circuit breaker, 4 A, 3-pole The GV2LE08 is a 3-pole motor circuit breaker from the TeSys GV2 range, rated 4 A continuous for motor protection. Magnetic trip set at 74 A provides instantaneous short-circuit interruption. Designed for AC-3 and AC-3e duty (motor starting/switching) and certified as a disconnecting means per IEC 60947-1. The 4 A continuous rating sets the maximum steady-state motor current this breaker can carry without tripping. The magnetic trip at 74 A ensures the breaker opens instantly on short-circuit, but allows normal motor starting inrush. Suitable for motors up to 1.5 kW at 400 V or 3 kW at 690 V. Electrical durability is 100,000 cycles at AC-3 415 V, mechanical 100,000 cycles.","metaTitle":"GV2LE08 TeSys GV2 Motor Circuit Breaker 4A 3P","metaDescription":"GV2LE08 4 A motor circuit breaker, magnetic trip 74 A, 100 kA breaking at 400 V. IEC/UL/CSA. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"3.09 in (78.5 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US1CP1018402","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate)","Control Type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"1.5 kW 400/415 V AC 50/60 Hz 1.5 kW 500 V AC 50/60 Hz 2.2 kW 500 V AC 50/60 Hz 3 kW 690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2LE","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"4 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"74 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"1.8 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"4 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 75 % 690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$18.52","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/870eb39e167e3567e6d3036f7612dbd2.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2LE08/alternatives.json"},"ai":{"faq":[{"question":"What is the rated current and magnetic trip of the GV2LE08?","answer":"The GV2LE08 is rated 4 A continuous and has a fixed magnetic trip set at 74 A for short-circuit protection."},{"question":"What standards does the GV2LE08 comply with?","answer":"It complies with IEC 60947-2 (circuit-breakers), IEC 60947-4-1 (motor-starters), UL 60947-4-1, and CSA C22.2 No 60947-4-1."},{"question":"What color is the GV2LE08 housing?","answer":"Dark grey."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2LE08","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2LE08 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}