{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2LE32","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2LE32","canonicalUrl":"https://aoctrl.com/schneider/GV2LE32","factsUrl":"https://aoctrl.com/api/mcp/products/GV2LE32","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2LE32, 3-pole motor circuit breaker, 32 A rated, magnetic trip 537.6 A, breaking capacity 50 kA at 230/240 V AC.","salesMarkdown":"The GV2LE32: Sized for 15 kW at 400/415 V or 18.5 kW at 500 V, 22 kW at 690 V. The magnetic trip is non-adjustable, so this breaker is a fixed-coordination match for motors up to that output. Thermal protection is inherent in the bi-metal element; the magnetic element handles short-circuits only. Mechanical durability is 100,000 cycles, electrical durability 100,000 cycles under AC-3 duty at rated current — line-side switching for frequent start/stop profiles. Occupies 45 mm (1.8 in) of DIN rail width. Clips onto 35 mm symmetrical rail or can be panel-mounted with an adaptor plate. Power terminals accept 1–6 mm² solid or 1.5–6 mm² flexible wire; torque to 1.7 N·m. IP20 finger-safe terminals, IK04 impact resistance. Ambient rating up to 2000 m altitude; no derating below 40 °C ambient.","metaTitle":"Schneider GV2LE32 TeSys Deca Motor Circuit Breaker, 32A, 3P","metaDescription":"Active-production motor circuit breaker, 32 A rated, 537.6 A magnetic trip, breaking capacity up to 50 kA at 230/240 V AC. EN/IEC 60947-4-1 and -2 compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"3.09 in (78.5 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US1CP1018402","Standards":"EN/IEC 60947-4-1 EN/IEC 60947-2 IEC/EN 60335-2-40:Annex JJ","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate)","Control Type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"15 kW 400/415 V AC 50/60 Hz 18.5 kW 500 V AC 50/60 Hz 22 kW 690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"50 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 10 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 6 kA Icu 440 V AC 50/60 Hz IEC 60947-2 4 kA Icu 500 V AC 50/60 Hz IEC 60947-2 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2LE","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"32 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"537.6 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"1.8 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"32 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz IEC 60947-2 50 % 400/415 V AC 50/60 Hz IEC 60947-2 50 % 440 V AC 50/60 Hz IEC 60947-2 75 % 500 V AC 50/60 Hz IEC 60947-2 75 % 690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$23.66","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/870eb39e167e3567e6d3036f7612dbd2.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2LE32/alternatives.json"},"ai":{"faq":[{"question":"What color is the GV2LE32?","answer":"The device is dark grey."},{"question":"What is the depth of the GV2LE32?","answer":"Depth is 78.5 mm (3.09 in)."},{"question":"What compliance documentation does the GV2LE32 carry?","answer":"The breaker complies with EN/IEC 60947-4-1, EN/IEC 60947-2, and IEC 60335-2-40 Annex JJ. Fire resistance per IEC 60695-2-11 at 960 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2LE32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2LE32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}