{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME02TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME02TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2ME02TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME02TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2ME02TQ motor circuit breaker, 0.25 A, thermal-magnetic, 3-pole, 100 kA breaking capacity, IP20.","salesMarkdown":"The Schneider Electric GV2ME02TQ is a TeSys GV2 motor circuit breaker — a thermal-magnetic device sized for protecting a 0.06 kW motor at 400/415 V AC 50/60 Hz. The phase-failure sensitivity per IEC 60947-4-1 means it will trip if one phase drops out — protecting the motor from single-phasing. Mechanical durability is 100,000 cycles, which is typical for a manual motor starter in a panel that sees occasional switching. The 45 mm width means it takes up a single modular space on the rail — standard for a 3-pole motor-protective device. Screw-clamp terminals accept up to 2 x 6 mm² solid or 2 x 4 mm² flexible with ferrule; torque to 1.7 N·m. Mount it horizontally or vertically; the thermal trip calibration holds either way. The IK04 impact rating handles accidental tool bumps during commissioning. Operating altitude is limited to 2000 m without derating. Carries dual certification to IEC/EN 60947-2 (for circuit-breaker function) and IEC/EN 60947-4-1 (for motor-starter coordination), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1. Also listed for use in IEC/EN 60335 appliance circuits per Annex JJ and Clause 30.2. Fire resistance tested to 960 °C per IEC 60695-2-11. Climatic withstand per IACS covers marine and humid environments.","metaTitle":"Schneider GV2ME02TQ TeSys GV2 Motor Circuit Breaker, 0.25 A","metaDescription":"Schneider Electric GV2ME02TQ TeSys GV2 motor circuit breaker, 0.25 A rated current, 0.06 kW at 400 V. Thermal-magnetic, 100 kA breaking capacity. Active production. UL/CSA/IEC cert","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Push-button","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.06 kW at 400/415 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 24","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2ME","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"0.25 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"3.08 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"0.16...0.25 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"0.25 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6b2a6255ab96167e7c26e55c950ef93e.pdf","sourceUrl":"https://www.se.com/be/en/product/GV2ME02TQ/motor-circuit-breaker-tesys-deca-3p-0-160-25-a-thermal-magnetic-screw-clamp-terminals-tq-24-units/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2ME02TQ/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the GV2ME02TQ?","answer":"Rated current (In) is 0.25 A. Magnetic trip threshold is 3.08 A. Breaking capacity is 100 kA Icu at 400/415 V AC. Motor power rating is 0.06 kW at 400/415 V AC 50/60 Hz. Rated insulation voltage (Ui) and operational voltage (Ue) are both 690 V AC."},{"question":"What standards does the GV2ME02TQ comply with?","answer":"It complies with IEC/EN 60947-2, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-2-40 Annex JJ. It is also certified for isolation per IEC 60947-1 and has fire resistance to 960 °C per IEC 60695-2-11."},{"question":"How is the GV2ME02TQ mounted?","answer":"It clips onto a 35 mm symmetrical DIN rail or can be panel-mounted with an adaptor plate. It can be mounted horizontally or vertically. Width is 45 mm (one modular space)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME02TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME02TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}