{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME03AE11TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME03AE11TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2ME03AE11TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME03AE11TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2ME, motor circuit breaker GV2ME03AE11TQ, 0.4 A rated current, 3 poles, thermal-magnetic, 100 kA breaking capacity at 400 V AC, 1 NO + 1 NC auxiliary contacts.","salesMarkdown":"## Motor circuit breaker for 0.4 A motor protection The Schneider Electric GV2ME03AE11TQ is a TeSys Deca motor circuit breaker rated for 0.4 A continuous current, designed to protect a 0.09 kW motor at 400/415 V AC 50/60 Hz. It uses thermal-magnetic trip technology, with a magnetic trip point at 5.8 A, so it handles inrush without nuisance trips while still clearing a locked-rotor fault. Phase failure sensitivity is built in per IEC 60947-4-1, so a lost phase on a three-phase motor will trip the breaker before the motor overheats. Accepts two conductors per terminal — solid up to 6 mm², flexible with ferrule up to 4 mm² — and the screw clamp torque is 1.7 N·m. The IK04 impact rating means it withstands 0.5 J impacts — fine for a panel interior, not for direct tool strikes. ## Durability and environmental ratings Rated for 100,000 electrical cycles under AC-3 duty at 415 V, and 100,000 mechanical cycles. That's typical for a motor-starting application — expect the breaker to outlast the motor in most light-duty conveyor or pump installations. Climatic withstand per IACS covers the usual marine and industrial temperature/humidity ranges. Fire resistance tested to 960 °C glow-wire per IEC 60695-2-11, which satisfies the hot-surface requirements in appliance standards like IEC/EN 60335. Certified to EN/IEC 60947-2 (circuit-breaker standard), EN/IEC 60947-4-1 (contactor/ starter standard), UL 60947-4-1, and CSA C22.2 No 60947-4-1. Also referenced in IEC/EN 60335-2-40 (heat pump/air conditioner) and IEC/EN 60335-1 Clause 30.2 for glow-wire testing. The UL/CSA marks cover North American panel builds; the IEC marks cover European machinery directives.","metaTitle":"Schneider Electric GV2ME03AE11TQ Motor Circuit Breaker, 0.4","metaDescription":"Schneider Electric TeSys GV2 GV2ME03AE11TQ motor circuit breaker, 0.4 A rated current, 100 kA breaking capacity at 400 V, thermal-magnetic protection, 1 NO + 1 NC aux contacts. Act","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Push-button","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.09 kW at 400/415 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 20","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2ME","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"0.4 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529 (open mounted)","Magnetic tripping current":"5.8 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","Auxiliary contact composition":"1 NO + 1 NC front","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"600 V AC 50/60 Hz conforming to UL 508 690 V AC 50/60 Hz conforming to IEC 60947-2 600 V AC 50/60 Hz conforming to CSA C22.2 No 14","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"0.25...0.4 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...40 °C in enclosure -20...60 °C open mounted","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"0.4 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f7d65526755da4e3e1b5792ee02e5997.pdf","sourceUrl":"https://www.se.com/nl/en/product/GV2ME03AE11TQ/motor-circuit-breaker-tesys-deca-0-25-0-4-a-3-3d-thermal-magnetic-trip-unit/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2ME03AE11TQ/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this motor circuit breaker?","answer":"Rated current 0.4 A, magnetic trip at 5.8 A, breaking capacity 100 kA at 400 V AC, motor power 0.09 kW at 400/415 V. Thermal-magnetic protection with phase failure sensitivity. 1 NO + 1 NC auxiliary contacts are built in."},{"question":"What standards does this part comply with?","answer":"Certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Also referenced in IEC/EN 60335-2-40 and IEC/EN 60335-1 Clause 30.2 for glow-wire testing."},{"question":"How is the GV2ME03AE11TQ mounted?","answer":"Clips onto 35 mm symmetrical DIN rail or screws to a panel using an adaptor plate. Accepts horizontal or vertical orientation. Width is 45 mm, depth 78.5 mm, height 89 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME03AE11TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME03AE11TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}