{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME03AP","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME03AP","canonicalUrl":"https://aoctrl.com/schneider/GV2ME03AP","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME03AP","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2 motor circuit breaker, 3-pole, 0.4 A rated current, thermal-magnetic protection, 100 kA breaking capacity, DIN rail mount.","salesMarkdown":"The Schneider Electric GV2ME03AP is a TeSys GV2 motor circuit breaker — a 3-pole thermal-magnetic device rated at 0.4 A continuous current, designed to protect small motor loads up to 0.09 kW at 400/415 V AC 50 Hz. It combines a thermal overload (for sustained overcurrent) with a magnetic trip set at 5.8 A for short-circuit protection, and it includes phase-failure sensitivity per IEC 60947-4-1. The GV2ME03AP is listed as current-production — no end-of-life notice or successor part is recorded, so it remains a standard BOM line item for new panels and replacement spares. It is sized for the smallest fractional-horsepower motors: a 0.09 kW (approx. 1/8 HP) three-phase motor at 400 V draws right around 0.4 A at full load. Magnetic trip threshold is fixed at 5.8 A (14.5× In), meaning the instantaneous magnetic element clears hard shorts above that level, while the thermal bimetal handles overloads below it. No adjustable magnetic trip here — the fixed ratio is standard for GV2 breakers. Rated insulation voltage [Ui] of 690 V AC and operational voltage [Ue] of 690 V AC — the breaker can be applied on 400 V, 480 V, or 600 V systems without derating the insulation. The 45 mm width (three modular spaces) fits standard enclosure rail layouts. Screw-clamp terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule — enough for the small-gauge wiring typical of a 0.4 A motor circuit. Listed to EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (motor-starter standard), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1 — so it is accepted in North American and global installations.","metaTitle":"Schneider Electric GV2ME03AP TeSys GV2 Motor Circuit Breaker","metaDescription":"Schneider Electric GV2ME03AP TeSys GV2 motor circuit breaker, 0.4 A rated current, thermal-magnetic trip, 100 kA breaking capacity, 3-pole, DIN rail mount, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","title":"GV2ME03AP","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","description":"Motor circuit breaker, TeSys Deca, 3P, 0.25 to 0.4A, thermal magnetic, screw clamp terminals","Control type":"Push-button","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.09 kW at 400/415 V AC 50 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu at 230/240 V AC 50 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50 Hz conforming to IEC 60947-2","Device short name":"GV2ME","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"0.4 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"5.8 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"0.25...0.4 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"0.4 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50 Hz conforming to IEC 60947-2 100 % at 440 V AC 50 Hz conforming to IEC 60947-2 100 % at 500 V AC 50 Hz conforming to IEC 60947-2 100 % at 690 V AC 50 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d58d5dee9df164f0f62c94b8b5b01835.pdf","sourceUrl":"https://www.se.com/mk/en/product/GV2ME03AP/motor-circuit-breaker-tesys-deca-3p-0-25-to-0-4a-thermal-magnetic-screw-clamp-terminals/"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"100 kA Icu at 230/240 V, 400/415 V, 440 V, 500 V, and 690 V AC 50 Hz — the rating is flat across the full voltage range."},{"question":"What standards does the GV2ME03AP comply with?","answer":"It complies with EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1."},{"question":"What is the depth of this device?","answer":"The depth is 78.5 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME03AP","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME03AP when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}