{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME05K2B7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME05K2B7","canonicalUrl":"https://aoctrl.com/schneider/GV2ME05K2B7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME05K2B7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2-ME, GV2ME05K2B7, DOL reversing combination motor starter, thermal adjustment 0.63…1 A, 24 V AC 50/60 Hz control circuit.","salesMarkdown":"It integrates a 3-pole motor circuit breaker, a 3-pole reversing contactor, and a GV2AF01 combination block into a single assembly — one order code, one DIN-rail footprint at 45 mm wide, 152 mm tall, and 87 mm deep. The thermal protection adjustment range is 0.63 to 1 A, so this unit is sized for small motors in the 0.25 to 0.37 kW range at 400/415 V or 440 V AC, 50/60 Hz. Rated AC-3 utilisation category means it is designed for starting and stopping squirrel-cage induction motors — the standard duty for a reversing starter on conveyors, pumps, or small hoists. The magnetic tripping current is set at 13 A, which provides short-circuit protection for the motor branch. Breaking capacity is 50 kA at 400/415 V and 440 V AC, conforming to IEC 60947-4-1; that high fault-current rating means this starter can be installed on panels with substantial upstream fault current without needing a separate current-limiting fuse ahead of it, as long as the coordination is Type 1 (the starter may need contact replacement after a fault, but the installation stays coordinated). ## Control circuit and deployment context The reversing configuration means two contactors are mechanically and electrically interlocked inside the combination block; the panel wiring connects the forward and reverse run commands separately.","metaTitle":"Schneider GV2ME05K2B7 TeSys reversing starter, 0.63-1 A, 24","metaDescription":"Schneider Electric GV2ME05K2B7 TeSys GV2-ME DOL reversing combination motor starter. Thermal adj 0.63-1 A, 24 V AC coil, 50 kA breaking capacity at 400 V. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"87 mm","Range":"TeSys","Width":"45 mm","Height":"152 mm","Motor power kW":"0.25 kW at 400/415 V AC 50/60 Hz 0.37 kW at 400/415 V AC 50/60 Hz 0.25 kW at 440 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz","lifecycle_stage":"current","Breaking capacity":"50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1","Coordination type":"Type 1","Device short name":"GV2ME","Poles description":"3P","Device composition":"1 motor circuit breaker type GV2ME 1 3-pole reversing contactor 1 combination block GV2AF01","Motor starter type":"Reversing","Utilisation category":"AC-3","Magnetic tripping current":"13 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"24 V AC 50/60 Hz","Thermal Protection Adjustment Range":"0.63...1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/GV2ME05K2B7/dol-reversing-combination-starter-tesys-gv2me-0-63-1-a-24-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2ME05K2B7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the GV2ME05K2B7?","answer":"Thermal protection adjustment range 0.63 to 1 A, magnetic tripping current 13 A, breaking capacity 50 kA at 400/415 V and 440 V AC, AC-3 utilisation category, control circuit 24 V AC 50/60 Hz, and motor power 0.25 to 0.37 kW at 400/415 V or 440 V."},{"question":"What is the physical size of the GV2ME05K2B7?","answer":"Width 45 mm, height 152 mm, depth 87 mm. It mounts on a standard DIN rail."},{"question":"What product family does the GV2ME05K2B7 belong to?","answer":"It is part of the Schneider Electric TeSys range, specifically the TeSys GV2-ME series of motor circuit breakers and combination starters."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME05K2B7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME05K2B7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}