{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME06AN11TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME06AN11TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2ME06AN11TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME06AN11TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2 motor circuit breaker, GV2ME06AN11TQ, 1.6 A rated current, 100 kA breaking capacity, thermal-magnetic trip, 3-pole.","salesMarkdown":"## Part identity and compliance envelope The Schneider Electric GV2ME06AN11TQ is a TeSys GV2 motor circuit breaker, a 3-pole thermal-magnetic device rated at 1.6 A continuous current. It is designed for motor protection (category AC-3 and AC-3e per IEC 60947-4-1) and circuit protection (category A per IEC 60947-2). The breaking capacity is 100 kA Icu across the full voltage range from 230/240 V to 690 V AC, certified to IEC 60947-2. Standards compliance is fully documented: EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, plus IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for fire resistance. The part carries a 960 °C glow-wire rating per IEC 60695-2-11. ## Installation and integration constraints Mounting options: clips onto 35 mm symmetrical DIN rail, or screws to a panel using an adaptor plate. Both horizontal and vertical orientations are permitted. Dimensions are 89 mm height, 54 mm width, 78.5 mm depth — fits standard motor-starter footprints. Power connections accept screw-clamp terminals: 2 x 1–6 mm² solid, or 2 x 1.5–6 mm² flexible without ferrule, or 2 x 1–4 mm² flexible with ferrule. Tightening torque is 1.7 N·m. Built-in auxiliary contacts: 1 NO + 1 NC side-mounted. IP20 protection when open-mounted (finger-safe), IK04 impact resistance. Climatic withstand conforms to IACS. Operating altitude is limited to 2000 m. ## Electrical performance and trip characteristics Thermal-magnetic trip: the magnetic (short-circuit) trip threshold is 26.2 A, which is approximately 16.4 x In. This provides rapid clearing of high faults while riding through motor inrush. Power dissipation per pole is 2.5 W, so total heat at rated load is 7.5 W — factor into enclosure thermal calculations. Electrical durability: 100,000 cycles at AC-3 / AC-3e at 415 V at rated current. Mechanical durability matches at 100,000 cycles. The device is rated for uninterrupted duty per IEC 60947-4-1. Motor power ratings span 0.37 kW to 1.1 kW depending on line voltage (400/415 V, 500 V, 690 V AC). The 1.6 A frame covers small motors, fans, and pumps in the fractional-to-1.1 kW range.","metaTitle":"Schneider GV2ME06AN11TQ Motor Circuit Breaker, 1.6 A, 100 kA","metaDescription":"Schneider TeSys GV2ME06AN11TQ motor circuit breaker, 1.6 A rated current, 100 kA breaking capacity at 400 V. Active production. UL/CSA/IEC certified. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"54 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Push-button","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz 0.75 kW at 690 V AC 50/60 Hz 1.1 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 20","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2ME","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"1.6 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529 (open mounted)","Magnetic tripping current":"26.2 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","Auxiliary contact composition":"1 NO + 1 NC side","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"600 V AC 50/60 Hz conforming to UL 508 690 V AC 50/60 Hz conforming to IEC 60947-2 600 V AC 50/60 Hz conforming to CSA C22.2 No 14","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"1...1.6 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...40 °C in enclosure -20...60 °C open mounted","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"1.6 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/GV2ME06AN11TQ/motor-circuit-breaker-tesys-deca-1-1-6-a-3-3d-thermal-magnetic-trip-unit/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2ME06AN11TQ/alternatives.json"},"ai":{"faq":[{"question":"What are the key standards this part is certified to?","answer":"It is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, plus IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for fire resistance."},{"question":"What is the breaking capacity of the GV2ME06AN11TQ?","answer":"100 kA Icu at all rated voltages from 230/240 V through 690 V AC, conforming to IEC 60947-2."},{"question":"Does this motor circuit breaker include phase-failure protection?","answer":"Yes, phase-failure sensitivity is built in, conforming to IEC 60947-4-1."},{"question":"What auxiliary contacts are included on the GV2ME06AN11TQ?","answer":"It comes with 1 NO + 1 NC side-mounted auxiliary contacts."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME06AN11TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME06AN11TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}