{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME06K1M7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME06K1M7","canonicalUrl":"https://aoctrl.com/schneider/GV2ME06K1M7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME06K1M7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME06K1M7, 1...1.6 A thermal protection, 220...230 V AC coil, 50 kA breaking capacity.","salesMarkdown":"The GV2ME06K1M7 is a non-reversing DOL combination starter from the TeSys GV2-ME series, integrating a 3-pole motor circuit breaker and a contactor in a single block. Thermal protection adjusts from 1 to 1.6 A, and the control circuit is rated for 220/230 V AC 50/60 Hz. The magnetic tripping current is set at 22.5 A. Rated breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. Coordination type is Type 1, meaning the starter is not guaranteed to remain functional after a fault — the breaker clears the short circuit, but the contactor may need replacement. This is standard for applications where fault isolation speed is prioritized over component survival. ## Motor power and utilisation category Rated for AC-3 utilisation (squirrel-cage motor starting and switching off during running). Motor power ratings span 0.37 kW to 0.75 kW depending on supply voltage: 0.37 kW at 400/415 V, 0.55 kW at 440 V, and up to 0.75 kW at 500 V. The 1-1.6 A thermal adjustment range covers the lower end of small motor protection. The device composition includes one combination block GV2AF01, one 3-pole contactor, and one motor circuit breaker type GV2ME. Dimensions: 45 mm wide, 152 mm high, 87 mm deep — fits a standard DIN-rail enclosure footprint. The 45 mm width occupies a single modular space, leaving room for auxiliary blocks or a separate control transformer on the same rail.","metaTitle":"Schneider Electric GV2ME06K1M7 TeSys DOL Starter, 1-1.6 A, 2","metaDescription":"GV2ME06K1M7 DOL combination starter, TeSys range, 1-1.6 A thermal adjustment, 220-230 VAC coil, 50 kA breaking capacity. Obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"87 mm","Range":"TeSys","Width":"45 mm","Height":"152 mm","Motor power kW":"0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Breaking capacity":"50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1","Coordination type":"Type 1","Device short name":"GV2ME","Poles description":"3P","Device composition":"1 combination block GV2AF01 1 3-pole contactor 1 motor circuit breaker type GV2ME","Motor starter type":"Non reversing","Utilisation category":"AC-3","Magnetic tripping current":"22.5 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"220/230 V AC 50/60 Hz","Thermal Protection Adjustment Range":"1...1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1d5eff1bbde35a1116001b2e30e0d38d.pdf","sourceUrl":"https://www.se.com/in/en/product/GV2ME06K1M7/dol-combination-starter-tesys-gv2me-1-1-6-a-220-230-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2ME06K1M7/alternatives.json"},"ai":{"faq":[{"question":"What is the thermal protection adjustment range?","answer":"The thermal protection adjustment range is 1 to 1.6 A, set via the dial on the front of the motor circuit breaker section."},{"question":"What is the breaking capacity?","answer":"Breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1."},{"question":"What control voltage does this starter use?","answer":"The control circuit voltage is 220/230 V AC 50/60 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME06K1M7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME06K1M7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}