{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME06K2FE7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME06K2FE7","canonicalUrl":"https://aoctrl.com/schneider/GV2ME06K2FE7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME06K2FE7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2-ME reversing DOL combination starter, GV2ME06K2FE7, 1...1.6 A thermal adjustment, 115 V AC 50/60 Hz control, 50 kA breaking capacity.","salesMarkdown":"It is rated for AC-3 utilisation category (squirrel-cage motor switching) and carries a thermal protection adjustment range of 1 to 1.6 A, which sets the overload relay trip point for the connected motor. The control circuit is 115 V AC 50/60 Hz, so the coil pulls in at that voltage — standard for North American and some European panel voltages. The magnetic tripping current is fixed at 22.5 A, meaning the instantaneous magnetic trip operates above that level for short-circuit protection, while the thermal element handles the overload curve. ## Motor power coverage and breaking capacity This starter covers motor power ratings from 0.37 kW up to 0.75 kW depending on supply voltage — 0.37 kW at 400/415 V and 440 V, 0.55 kW at 400/415 V and 440 V, and 0.37/0.55/0.75 kW at 500 V, all at 50/60 Hz. The 1-1.6 A thermal adjustment range maps to small motors in that power band; if your motor draws more than 1.6 A FLA, this is the wrong thermal block. Breaking capacity is 50 kA at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. Coordination is Type 1, so the starter may need contact replacement after a fault but the breaker clears it. The 45 mm width is three module spaces (each 15 mm), typical for a 3-pole motor starter with integrated reversing contactor. Depth of 87 mm means it will clear most shallow enclosures, but check your door clearance if using a deep rotary handle.","metaTitle":"Schneider GV2ME06K2FE7 TeSys reversing starter, 1-1.6 A, 115","metaDescription":"Schneider Electric TeSys GV2ME06K2FE7 DOL reversing combination motor starter. Thermal adj 1-1.6 A, 115 V AC control, 50 kA breaking capacity. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"87 mm","Range":"TeSys","Width":"45 mm","title":"GV2ME06K2FE7","Height":"152 mm","description":"DOL reversing combination starter - TeSys GV2-ME - 1...1.6 A - 115 V AC","Motor power kW":"0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Breaking capacity":"50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1","Coordination type":"Type 1","Device short name":"GV2ME","Poles description":"3P","Device composition":"1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole reversing contactor","Motor starter type":"Reversing","Utilisation category":"AC-3","Magnetic tripping current":"22.5 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"115 V AC 50/60 Hz","Thermal Protection Adjustment Range":"1...1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f99dd9e279a6a668cf9f6dacdb6c3bc0.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV2ME06K2FE7/dol-reversing-combination-starter-tesys-gv2me-1-1-6-a-115-v-ac/"},"ai":{"faq":[{"question":"What motor power does this starter cover?","answer":"It covers 0.37 kW to 0.75 kW depending on supply voltage: 0.37 kW at 400/415 V and 440 V, 0.55 kW at 400/415 V and 440 V, and 0.37/0.55/0.75 kW at 500 V, all at 50/60 Hz. The thermal adjustment range of 1-1.6 A determines the actual motor FLA it can protect."},{"question":"What is the breaking capacity of GV2ME06K2FE7?","answer":"50 kA at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. Coordination type is 1."},{"question":"What control voltage does this starter use?","answer":"The control circuit is 115 V AC 50/60 Hz."},{"question":"What are the physical dimensions of GV2ME06K2FE7?","answer":"Height 152 mm, width 45 mm, depth 87 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME06K2FE7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME06K2FE7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}