{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME07AE11TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME07AE11TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2ME07AE11TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME07AE11TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2 motor circuit breaker, GV2ME07AE11TQ, 2.5 A, 3-pole, thermal-magnetic, 100 kA breaking capacity at 400 V AC.","salesMarkdown":"It is a 3-pole device with a rated current of 2.5 A, using a thermal-magnetic trip unit to provide overload and short-circuit protection for motors up to 0.75 kW at 400/415 V AC. The thermal element handles sustained overloads, while the magnetic trip is fixed at 39 A, clearing short-circuit faults. The breaker is rated for AC-3 and AC-3e utilisation categories, meaning it is suited for starting and stopping squirrel-cage motors under load, and it includes phase failure sensitivity per IEC 60947-4-1. The power dissipation per pole is 2.5 W, which matters for thermal management inside a sealed enclosure. Mechanical durability is rated at 100,000 cycles, with electrical durability also at 100,000 cycles for AC-3 duty at 415 V. This gives a realistic service life for frequent motor starting applications like conveyors or pumps. Dimensions are 89 mm high, 45 mm wide, and 78.5 mm deep, so it occupies a single 45 mm module width on the rail. It can be mounted horizontally or vertically. Power circuit connections use screw clamp terminals accepting 1 to 6 mm² solid or 1.5 to 6 mm² flexible wire, with a tightening torque of 1.7 N·m. The auxiliary contact block is integrated with 1 NO + 1 NC front-mounted contacts. The GV2ME07AE11TQ is certified to EN/IEC 60947-2 (circuit-breakers) and EN/IEC 60947-4-1 (contactors and motor-starters), as well as UL 60947-4-1 and CSA C22.2 No 60947-4-1. It also complies with IEC/EN 60335-2-40 (Annex JJ) and IEC/EN 60335-1 (Clause 30.2) for heat and fire resistance, with a glow-wire test rating of 960 °C per IEC 60695-2-11.","metaTitle":"Schneider Electric GV2ME07AE11TQ TeSys GV2 Motor Circuit Bre","metaDescription":"Schneider Electric GV2ME07AE11TQ TeSys GV2 motor circuit breaker, 2.5 A rated current, thermal-magnetic protection, 100 kA breaking capacity at 400 V, 3-pole, IP20. Active producti","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Push-button","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.75 kW at 400/415 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz 1.5 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 20","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2ME","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"2.5 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529 (open mounted)","Magnetic tripping current":"39 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","Auxiliary contact composition":"1 NO + 1 NC front","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"600 V AC 50/60 Hz conforming to UL 508 690 V AC 50/60 Hz conforming to IEC 60947-2 600 V AC 50/60 Hz conforming to CSA C22.2 No 14","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"1.6...2.5 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...40 °C in enclosure -20...60 °C open mounted","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"2.5 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/GV2ME07AE11TQ/motor-circuit-breakertesys-deca-frame-23p1-62-5athermal-magneticpush-buttonwith-gvae11bulk-qty/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2ME07AE11TQ/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to the GV2ME07AE11TQ in the TeSys family?","answer":"Within the TeSys GV2 range, the closest alternative would be a different rated-current variant of the same GV2ME form factor. The GV2ME07AE11TQ is a 2.5 A unit; a higher or lower current rating in the same series would share the same footprint, auxiliary contact configuration, and breaking capacity, but the thermal-magnetic trip setting would differ to match the motor full-load current."},{"question":"What is the depth of the GV2ME07AE11TQ?","answer":"The depth is 78.5 mm."},{"question":"What range does the GV2ME07AE11TQ belong to?","answer":"It belongs to the TeSys Deca range."},{"question":"What compliance documentation is available for this part?","answer":"The part carries certifications to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, as well as IEC/EN 60335-2-40 and IEC/EN 60335-1. It also meets the glow-wire test at 960 °C per IEC 60695-2-11."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME07AE11TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME07AE11TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}