{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME08K2M7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME08K2M7","canonicalUrl":"https://aoctrl.com/schneider/GV2ME08K2M7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME08K2M7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2-ME reversing motor starter, GV2ME08K2M7, 2.5...4 A thermal protection, 220...230 V AC coil, 3-pole, 50 kA breaking capacity.","salesMarkdown":"The Schneider Electric GV2ME08K2M7 is a TeSys GV2-ME reversing DOL combination starter, integrating a motor circuit breaker (GV2ME) with a reversing contactor block (GV2AF01) into a single 45 mm wide package. The thermal protection adjustment range is 2.5...4 A, which sets the overload trip point for the connected motor. The magnetic short-circuit trip is fixed at 51 A, providing instantaneous protection on high fault currents. Breaking capacity is 50 kA Iq at 400/415 V AC, conforming to IEC 60947-4-1 — this means the starter can safely interrupt a fault current up to 50 kA without welding its contacts or causing a cascade failure upstream, which is a strong SCCR for a compact motor starter. ## Where you would use it This is a panel-mounted reversing starter for a 1.1 kW motor at 400/415 V AC, or up to 2.2 kW at 500 V AC. The coordination type is Type 1, meaning under a short-circuit fault the starter may need contact replacement but the panel bus remains intact. For applications requiring no damage to the starter after a fault, you would need a Type 2 coordination study with upstream fuses or a specific circuit breaker.","metaTitle":"Schneider Electric GV2ME08K2M7 TeSys reversing motor starter","metaDescription":"Schneider Electric GV2ME08K2M7 TeSys reversing motor starter, 2.5...4 A thermal protection, 220/230 V AC coil, 50 kA breaking capacity at 400 V. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"87 mm","Range":"TeSys","Width":"45 mm","title":"GV2ME08K2M7","Height":"152 mm","description":"DOL reversing combination starter - TeSys GV2-ME - 2.5...4 A - 220...230 V AC","Motor power kW":"1.1 kW at 400/415 V AC 50/60 Hz 1.5 kW at 400/415 V AC 50/60 Hz 1.5 kW at 440 V AC 50/60 Hz 1.5 kW at 500 V AC 50/60 Hz 2.2 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Breaking capacity":"50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1","Coordination type":"Type 1","Device short name":"GV2ME","Poles description":"3P","Device composition":"1 motor circuit breaker type GV2ME 1 combination block GV2AF01 1 3-pole reversing contactor","Motor starter type":"Reversing","Utilisation category":"AC-3","Magnetic tripping current":"51 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"220/230 V AC 50/60 Hz","Thermal Protection Adjustment Range":"2.5...4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9bd1a90b42251a023fbfda1d48c11c69.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV2ME08K2M7/dol-reversing-combination-starter-tesys-gv2me-2-5-4-a-220-230-v-ac/"},"ai":{"faq":[{"question":"What are the key ratings for the GV2ME08K2M7?","answer":"Thermal protection range 2.5...4 A, magnetic trip at 51 A, breaking capacity 50 kA at 400/415 V AC, control voltage 220/230 V AC, and motor power up to 2.2 kW at 500 V AC."},{"question":"What is the physical size of the GV2ME08K2M7?","answer":"Width 45 mm, height 152 mm, depth 87 mm. It mounts on a standard DIN rail."},{"question":"What compliance documentation is available for the GV2ME08K2M7?","answer":"The part is rated to IEC 60947-4-1 for breaking capacity. Schneider Electric typically provides CE, UL, CSA, and CCC certifications for the TeSys GV2-ME series; confirm specific documentation with your order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME08K2M7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME08K2M7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}