{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME10AE11TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME10AE11TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2ME10AE11TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME10AE11TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2 motor circuit breaker, GV2ME10AE11TQ, 6.3 A rated, thermal-magnetic, 100 kA at 400 V, 3-pole, IP20, DIN-rail mount.","salesMarkdown":"It's sensitive to phase failure, so it will drop the motor if one phase is lost, which is standard for IEC 60947-4-1 compliance. Rated IP20 open-mounted, so it's meant for inside an enclosure, not out in the weather. The screw-clamp terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule, torqued to 1.7 N·m. Comes with 1 NO + 1 NC auxiliary contact built into the front, which saves you buying a separate block for basic status feedback. ## Rated for the load Motor power ratings: 2.2 kW at 400/415 V, 3 kW at 500 V, 4 kW at 690 V — all three-phase 50/60 Hz. The 6.3 A rated current covers a small motor, say a pump or a conveyor drive up to that kW range. Electrical durability is 100,000 cycles at rated current in AC-3 duty, mechanical durability also 100,000 cycles. That's solid for a manual motor starter in a machine that cycles a few times an hour. The 100 kA Icu at 400 V means you can put this on a panel with a high-fault-capacity transformer without worrying about the breaker failing to clear a dead short. This is a current-production part — no end-of-life notice on it. It carries approvals under EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, so it's accepted in North American and European panels. Also listed for IEC/EN 60335-2-40 (heat pump/air conditioner) and IEC/EN 60335-1 Clause 30.2 (glow-wire). Fire resistance is certified to 960 °C per IEC 60695-2-11.","metaTitle":"Schneider TeSys GV2ME10AE11TQ Motor Circuit Breaker, 6.3 A","metaDescription":"Schneider Electric TeSys GV2 motor circuit breaker, 6.3 A rated current, thermal-magnetic trip, 100 kA breaking capacity at 400 V. Active production. UL/CSA/CE. DIN-rail or panel m","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Push-button","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"2.2 kW at 400/415 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz 4 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 20","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2ME","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"6.3 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-4-1 AC-3 conforming to IEC 60947-2 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529 (open mounted)","Magnetic tripping current":"91 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","Auxiliary contact composition":"1 NO + 1 NC front","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"600 V AC 50/60 Hz conforming to UL 508 690 V AC 50/60 Hz conforming to IEC 60947-2 600 V AC 50/60 Hz conforming to CSA C22.2 No 14","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"4...6.3 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"6.3 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/GV2ME10AE11TQ/motor-circuit-breakertesys-deca-frame-23p46-3athermal-magneticpush-buttonwith-gvae11bulk-qty/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2ME10AE11TQ/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"Rated current is 6.3 A, magnetic trip at 91 A. Motor power is 2.2 kW at 400 V, 3 kW at 500 V, 4 kW at 690 V. Breaking capacity is 100 kA at 400 V AC. It's a 3-pole thermal-magnetic breaker with phase-failure sensitivity."},{"question":"What standards does this motor circuit breaker meet?","answer":"It complies with EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-2-40 Annex JJ. Fire resistance is 960 °C per IEC 60695-2-11."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME10AE11TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME10AE11TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}