{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME10K1B7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME10K1B7","canonicalUrl":"https://aoctrl.com/schneider/GV2ME10K1B7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME10K1B7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2-ME DOL combination motor starter, GV2ME10K1B7, thermal protection 4...6.3 A, 24 V AC 50/60 Hz control circuit.","salesMarkdown":"The GV2ME10K1B7 is a non-reversing DOL combination starter from the TeSys GV2-ME range, integrating a 3-pole motor circuit breaker and a 3-pole contactor in one block with the GV2AF01 base. The thermal protection adjustment range of 4...6.3 A sets the motor full-load current it protects — set the dial to match the nameplate FLA of the motor. The magnetic trip is fixed at 78 A, which clears short-circuit faults without nuisance tripping on inrush. Rated for AC-3 utilisation category, meaning it is designed for starting and stopping squirrel-cage induction motors under load. The motor power ratings span 2.2 kW at 400/415 V AC up to 3 kW at 500 V AC — match the voltage on your line to the kW column in the spec table. The 24 V AC control coil (50/60 Hz) is standard for PLC or relay-driven panels; verify your control transformer supplies 24 V AC, not DC. Breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. Coordination type is Type 1 per IEC 60947-4-1. Under a short-circuit, the contactor may need replacement after the fault, but the starter remains functional and the downstream motor is protected. If you need the contactor to survive a fault without replacement (Type 2 coordination), this is not the variant for that application. The 45 mm width and 87 mm depth fit a typical motor control centre bucket or small enclosure. The 152 mm height is the tallest dimension — check clearance above the rail for wiring and the auxiliary contact block if fitted. The combination block GV2AF01 is included; no separate base ordering needed.","metaTitle":"Schneider GV2ME10K1B7 TeSys DOL Starter, 4-6.3 A, 24 V AC","metaDescription":"Schneider Electric GV2ME10K1B7 TeSys GV2-ME DOL combination motor starter. Thermal range 4-6.3 A, 24 V AC coil, 50 kA breaking capacity at 400 V. Active production. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"87 mm","Range":"TeSys","Width":"45 mm","title":"GV2ME10K1B7","Height":"152 mm","description":"DOL combination starter - TeSys GV2-ME - 4...6.3 A - 24 V AC","Motor power kW":"2.2 kW at 400/415 V AC 50/60 Hz 2.2 kW at 440 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Breaking capacity":"50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1","Coordination type":"Type 1","Device short name":"GV2ME","Poles description":"3P","Device composition":"1 combination block GV2AF01 1 3-pole contactor 1 motor circuit breaker type GV2ME","Motor starter type":"Non reversing","Utilisation category":"AC-3","Magnetic tripping current":"78 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"24 V AC 50/60 Hz","Thermal Protection Adjustment Range":"4...6.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ddea84d6d6fc5ac429ccbafa260ea440.pdf","sourceUrl":"https://www.se.com/uk/en/product/GV2ME10K1B7/dol-combination-starter-tesys-gv2me-4-6-3-a-24-v-ac/"},"ai":{"faq":[{"question":"What is the thermal protection adjustment range?","answer":"The thermal overload relay adjusts from 4 A to 6.3 A. Set the dial to match the motor nameplate full-load current within that window."},{"question":"What control voltage does the coil require?","answer":"The control circuit voltage is 24 V AC at 50/60 Hz. Do not apply DC voltage to this coil variant."},{"question":"What is the breaking capacity at 400 V?","answer":"50 kA Iq at 400/415 V AC, 50/60 Hz, conforming to IEC 60947-4-1. The same 50 kA rating applies at 440 V and 500 V AC."},{"question":"What is the closest alternative in the same family?","answer":"Within the TeSys GV2-ME range, the key variant difference is the thermal adjustment range and coil voltage. For a different motor FLA, select the GV2ME part with the appropriate thermal range (e.g., GV2ME08 for 2.5-4 A, GV2ME14 for 6-10 A). For a different coil voltage, the suffix changes (e.g., GV2ME10K1 for 24 V AC, GV2ME10K2 for 48 V AC, GV2ME10K3 for 110 V AC). The physical footprint and breaking capacity are shared across the range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME10K1B7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME10K1B7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}