{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME14A","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME14A","canonicalUrl":"https://aoctrl.com/schneider/GV2ME14A","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME14A","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2 motor circuit breaker, GV2ME14A, 3-pole, 10 A, thermal-magnetic, magnetic trip 149 A, IP20.","salesMarkdown":"The GV2ME14A is a 3-pole motor circuit breaker from the TeSys GV2 line, rated 10 A continuous with a fixed magnetic trip at 149 A. It is built for motor protection under AC-3 duty, covering induction motors up to 7.5 kW at 690 V. Breaking capacity reaches 100 kA at 230/240 V (IEC 60947-2), which gives ample headroom for high-available-fault panels and simplifies selectivity with upstream devices. ## Ratings and mounting Thermal-magnetic trip unit with phase-failure sensitivity (per IEC 60947-4-1). Magnetic pickup at 149 A ensures clean separation from overload region for motor starting inrush. Dimensions: 45 mm wide, 78.5 mm deep, 101 mm high. Front face is IP20, color dark grey. Compliant with IEC 60947-2, IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, covering both European and North American installations.","metaTitle":"GV2ME14A TeSys GV2 Motor Circuit Breaker, 10 A, 3-Pole","metaDescription":"TeSys GV2 motor circuit breaker, 3-pole, 10 A rated current, magnetic trip 149 A, breaking capacity up to 100 kA. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Color":"Dark grey","Depth":"3.09 in (78.5 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","title":"GV2ME14A","Height":"4.0 in (101 mm)","Category":"US10I1122367","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate)","description":"Motor circuit breaker, TeSys Deca, 3P, AC-3/AC-3e, 6 to 10A, thermal magnetic, snap-in terminals, push button","Control Type":"Push-button","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"3 kW 400/415 V AC 50/60 Hz 4 kW 400/415 V AC 50/60 Hz 4 kW 500 V AC 50/60 Hz 5.5 kW 500 V AC 50/60 Hz 5.5 kW 690 V AC 50/60 Hz 7.5 kW 690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 15 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2ME","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"10 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit snap-in terminal 2 0.0008...0.004 in² (0.5...2.5 mm²)solid Power circuit snap-in terminal 2 0.0008...0.006 in² (0.5...4 mm²)flexible without cable end Power circuit snap-in terminal 2 0.0008...0.004 in² (0.5...2.5 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529 on front face)","Magnetic tripping current":"149 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Thermal protection adjustment range":"6...10 A IEC 60947-2","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"10 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 75 % 690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$188.92","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/501d4ef83ec4e29ee2d0ab9c6ba5ae8b.pdf","sourceUrl":"https://www.se.com/us/en/product/GV2ME14A/motor-circuit-breaker-tesys-deca-3p-ac3-ac3e-6-to-10a-thermal-magnetic-snapin-terminals-push-button/"},"ai":{"faq":[{"question":"What are the key compliance standards it meets?","answer":"The breaker complies with IEC 60947-2, IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1."},{"question":"What is the color and depth of the GV2ME14A?","answer":"The color is dark grey; depth is 78.5 mm (3.09 in)."},{"question":"What is the maximum motor power it can protect?","answer":"At 690 V AC it handles up to 7.5 kW; at 400/415 V it covers 3 kW and 4 kW depending on frequency."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME14A","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME14A when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}