{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME14AE11TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME14AE11TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2ME14AE11TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME14AE11TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2ME14AE11TQ motor circuit breaker, 3-pole, thermal-magnetic trip, 10 A rated current, 100 kA breaking capacity at 400 V AC.","salesMarkdown":"The 10 A rating at 400/415 V translates to a motor power of 3 kW, with the same breaker covering up to 5.5 kW at 690 V — one SKU for a range of motor sizes, which simplifies BOM management. The magnetic trip is fixed at 149 A, so it clears a bolted fault on a 10 A motor circuit without nuisance tripping on start-up. Phase failure sensitivity is built in, per IEC 60947-4-1, which is a hard requirement for any motor protection device — it detects a lost phase and trips before the motor single-phases to failure. This breaker carries a 100 kA Icu at 400/415 V AC per IEC 60947-2, which means it can safely interrupt a 100 kA prospective fault current at that voltage. For a 10 A motor circuit fed from a large transformer, that high interrupting rating lets you use it without an upstream fuse — the breaker clears the fault itself. At 690 V the Icu drops to 3 kA, so for 690 V applications the upstream protection needs to be coordinated. The utilisation category is Category A per IEC 60947-2, meaning it is not intended for frequent switching under load — that is the contactor's job. The breaker protects; the contactor switches. Terminals accept up to two 6 mm² solid or 4 mm² flexible conductors per pole, with a tightening torque of 1.7 N·m.","metaTitle":"Schneider TeSys GV2ME14AE11TQ Motor Circuit Breaker, 10 A, 3","metaDescription":"Schneider Electric GV2ME14AE11TQ TeSys Deca motor circuit breaker. Thermal-magnetic, 10 A, 3-pole, 100 kA breaking capacity at 400 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Push-button","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz 7.5 kW at 690 V AC 50/60 Hz 5.5 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 20","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2ME","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"10 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529 (open mounted)","Magnetic tripping current":"149 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","Auxiliary contact composition":"1 NO + 1 NC front","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"600 V AC 50/60 Hz conforming to UL 508 690 V AC 50/60 Hz conforming to IEC 60947-2 600 V AC 50/60 Hz conforming to CSA C22.2 No 14","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"6...10 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...40 °C in enclosure -20...60 °C open mounted","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"10 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b810d293a03682b50ac032c8d79d8345.pdf","sourceUrl":"https://www.se.com/vn/en/product/GV2ME14AE11TQ/motor-circuit-breakertesys-deca-frame-23p610athermal-magneticpush-buttonwith-gvae11bulk-qty/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2ME14AE11TQ/alternatives.json"},"ai":{"faq":[{"question":"What is the closest pin-compatible alternative in the TeSys family?","answer":"Within the TeSys Deca GV2ME range, the same frame size and terminal layout is shared across the 0.1 A to 32 A ratings. The GV2ME14AE11TQ is the 10 A variant. There is no single pin-compatible substitute with a different trip rating — the trip unit is integral. For a different current, you select a different GV2ME model, not an add-on module."},{"question":"What compliance documentation does this breaker carry?","answer":"It is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. It also meets the glow-wire test at 960 °C per IEC 60695-2-11, which is required for household appliance applications under IEC/EN 60335."},{"question":"What is the depth of this unit?","answer":"The depth is 78.5 mm, with a height of 89 mm and width of 45 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME14AE11TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME14AE11TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}