{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME14AP","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME14AP","canonicalUrl":"https://aoctrl.com/schneider/GV2ME14AP","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME14AP","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2ME14AP, motor circuit breaker, 3P, 10 A, thermal-magnetic, 100 kA breaking capacity at 400 V AC.","salesMarkdown":"It uses a thermal-magnetic trip unit to provide overload and short-circuit protection for motors drawing up to 10 A. Rated for uninterrupted duty per IEC 60947-4-1, it handles motor power from 3 to 4 kW at 400/415 V AC, 4 to 5.5 kW at 500 V AC, and 5.5 to 7.5 kW at 690 V AC — all at 50 Hz. For motor protection, you size the breaker to match the motor's full-load current — the thermal element tracks the motor heating curve. Breaking capacity hits 100 kA Icu at 230/240 V and 400/415 V AC, meaning it can safely interrupt a fault current up to 100,000 A at those voltages without welding contacts or rupturing the case. At 440 V it drops to 15 kA, at 500 V to 10 kA, and at 690 V to 3 kA — so verify the available fault current at your service voltage. Magnetic tripping current is fixed at 149 A — that's the instantaneous pickup for short-circuit protection. Below that, the thermal element handles overloads with an inverse-time curve. Phase failure sensitivity is built in per IEC 60947-4-1, so the breaker will trip if one phase drops out — critical for preventing single-phasing damage on three-phase motors. Mounts horizontally or vertically. Power connections accept up to two 1–6 mm² solid or 1.5–6 mm² flexible cables per screw clamp terminal. Tighten to 1.7 N·m.","metaTitle":"Schneider TeSys GV2ME14AP Motor Circuit Breaker, 10 A, 3P","metaDescription":"GV2ME14AP motor circuit breaker, 10 A rated current, 100 kA breaking capacity at 400 V. Active production. UL/CSA/IEC certified. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","title":"GV2ME14AP","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","description":"Motor circuit breaker, TeSys Deca, 3P, 6 to 10A, thermal magnetic, screw clamp terminals","Control type":"Push-button","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"3...4 kW at 400/415 V AC 50 Hz 4...5.5 kW at 500 V AC 50 Hz 5.5...7.5 kW at 690 V AC 50 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu at 230/240 V AC 50 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50 Hz conforming to IEC 60947-2 15 kA Icu at 440 V AC 50 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50 Hz conforming to IEC 60947-2","Device short name":"GV2ME","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"10 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"149 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"6...10 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"10 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50 Hz conforming to IEC 60947-2 100 % at 440 V AC 50 Hz conforming to IEC 60947-2 100 % at 500 V AC 50 Hz conforming to IEC 60947-2 75 % at 690 V AC 50 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/95284eb5ce0540bfcc0f013f022eacf6.pdf","sourceUrl":"https://www.se.com/mk/en/product/GV2ME14AP/motor-circuit-breaker-tesys-deca-3p-6-to-10a-thermal-magnetic-screw-clamp-terminals/"},"ai":{"faq":[{"question":"What are the key compliance standards for this breaker?","answer":"It is certified to EN/IEC 60947-2 (circuit-breaker standard), EN/IEC 60947-4-1 (motor-starter standard), UL 60947-4-1, and CSA C22.2 No 60947-4-1. Suitable for isolation per IEC 60947-1."},{"question":"What motor power range does the GV2ME14AP cover?","answer":"At 400/415 V AC it covers 3–4 kW; at 500 V AC, 4–5.5 kW; at 690 V AC, 5.5–7.5 kW — all at 50 Hz."},{"question":"How do I source the GV2ME14AP?","answer":"It is quoted to order against an RFQ through our industrial automation desk. Provide the quantity and target lead time for a firm offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME14AP","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME14AP when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}