{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME14K1F7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME14K1F7","canonicalUrl":"https://aoctrl.com/schneider/GV2ME14K1F7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME14K1F7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2-ME series, GV2ME14K1F7, DOL combination motor starter, 6...10 A thermal adjustment, 110 V AC 50/60 Hz control voltage.","salesMarkdown":"The GV2ME14K1F7 is a non-reversing DOL combination motor starter from the TeSys GV2-ME range, built as a single block that pairs a 3-pole motor circuit breaker with a 3-pole contactor and the GV2AF01 combination block. It covers motor protection from 6 to 10 A via the adjustable thermal relay, and the magnetic trip is fixed at 138 A — so it catches a locked-rotor condition on a motor sized within that band without nuisance-tripping on startup inrush. Rated for AC-3 utilisation category, meaning it is designed for switching squirrel-cage induction motors — starting, stopping, and reversing under load. The motor power rating hits 3 kW at 400/415 V AC and goes up to 5.5 kW at 500 V AC, so it fits common European 400 V line-fed pumps, fans, and small conveyors. At 440 V it drops to 15 kA, and at 500 V to 6 kA, so on a 480 V line (common in North American retrofit) you need to verify the available fault current at the panel. ## Panel fit and sourcing Dimensions are 152 mm high, 45 mm wide, 87 mm deep — the 45 mm width is a single modular DIN space, so it clips onto standard 35 mm DIN rail inside a control cabinet. The control circuit runs on 110 V AC 50/60 Hz, which matches common panel control transformers in European and Middle East installations; if your site runs 24 V DC or 230 V control, you need a different coil variant in the GV2ME family.","metaTitle":"Schneider TeSys GV2ME14K1F7 Motor Starter, 6-10 A, 110 V AC","metaDescription":"Active TeSys GV2ME14K1F7 DOL motor starter, 6-10 A thermal range, 3 kW at 400 V, AC-3, 50 kA breaking capacity. Panel-mount, 87 mm depth. Source to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"87 mm","Range":"TeSys","Width":"45 mm","title":"GV2ME14K1F7","Height":"152 mm","description":"DOL combination starter - TeSys GV2-ME - 6...10 A - 110 V AC","Motor power kW":"3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Breaking capacity":"50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 15 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1","Coordination type":"Type 1","Device short name":"GV2ME","Poles description":"3P","Device composition":"1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole contactor","Motor starter type":"Non reversing","Utilisation category":"AC-3","Magnetic tripping current":"138 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"110 V AC 50/60 Hz","Thermal Protection Adjustment Range":"6...10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/108fa871a46ecf37bc58b4305e1676e6.pdf","sourceUrl":"https://www.se.com/in/en/product/GV2ME14K1F7/dol-combination-starter-tesys-gv2me-6-10-a-110-v-ac/"},"ai":{"faq":[{"question":"What is the thermal protection adjustment range?","answer":"The adjustable thermal overload relay covers 6 to 10 A, set via a dial on the front of the breaker block."},{"question":"What breaking capacity does it offer at 400 V?","answer":"It is rated for 50 kA at 400/415 V AC per IEC 60947-4-1, which covers most industrial distribution panels with a transformer upstream."},{"question":"Does it include both a breaker and a contactor in one unit?","answer":"Yes, it is a combination starter: one GV2ME motor circuit breaker, one 3-pole contactor, and the GV2AF01 interlock block assembled as a single DIN-rail mountable device."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME14K1F7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME14K1F7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}