{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME14K2Q7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME14K2Q7","canonicalUrl":"https://aoctrl.com/schneider/GV2ME14K2Q7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME14K2Q7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2-ME reversing combination motor starter, GV2ME14K2Q7, thermal protection 6...10 A, 380/400 V AC control, 3-pole.","salesMarkdown":"The Schneider Electric GV2ME14K2Q7 is a TeSys GV2-ME reversing combination motor starter — a single-block assembly that combines a 3-pole motor circuit breaker (type GV2ME) with a reversing contactor and a GV2AF01 combination block. The thermal protection adjustment range of 6...10 A sets the overload relay's trip threshold, so you dial it to match the motor's full-load current. The magnetic short-circuit trip is fixed at 138 A — that's the instantaneous pickup that clears a fault without waiting for the thermal element. Rated for utilisation category AC-3, meaning it's tested for starting and stopping squirrel-cage motors — the standard duty for conveyor, pump, and fan loads. The GV2ME14K2Q7 snaps onto a 45 mm wide DIN-rail footprint — standard for panel-mounting in motor control centres. The 152 mm height and 87 mm depth leave room for auxiliary contact blocks or a downstream contactor interlock on the same rail. The reversing contactor pair is internally interlocked; you just supply the forward/reverse signals. ## Coordination and sourcing This is a Type 1 coordinated starter per IEC 60947-4-1, meaning after a short-circuit the starter may need contactor replacement but the breaker self-protects.","metaTitle":"Schneider GV2ME14K2Q7 TeSys reversing motor starter, 6-10 A","metaDescription":"Schneider TeSys GV2ME14K2Q7 reversing motor starter. Thermal adjustment 6-10 A, 50 kA breaking capacity at 400 V AC-3. Active production. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"87 mm","Range":"TeSys","Width":"45 mm","title":"GV2ME14K2Q7","Height":"152 mm","description":"DOL reversing combination starter - TeSys GV2-ME - 6...10 A - 380...400V AC","Motor power kW":"3 kW at 400/415 V AC 50/60 Hz 4 kW at 400/415 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 4 kW at 500 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Breaking capacity":"50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 15 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1","Coordination type":"Type 1","Device short name":"GV2ME","Poles description":"3P","Device composition":"1 combination block GV2AF01 1 3-pole reversing contactor 1 motor circuit breaker type GV2ME","Motor starter type":"Reversing","Utilisation category":"AC-3","Magnetic tripping current":"138 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"380/400 V AC 50/60 Hz","Thermal Protection Adjustment Range":"6...10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b03fa07b4e3182907d2cf379aad0b702.pdf","sourceUrl":"https://www.se.com/uk/en/product/GV2ME14K2Q7/dol-reversing-combination-starter-tesys-gv2me-6-10-a-380-400v-ac/"},"ai":{"faq":[{"question":"What is the thermal protection range and what does it mean?","answer":"The thermal adjustment range is 6...10 A. You set it to the motor's nameplate full-load current within that window. The magnetic trip is fixed at 138 A — that's the instantaneous short-circuit threshold, not adjustable."},{"question":"What breaking capacity does this starter have?","answer":"50 kA at 400/415 V AC (IEC 60947-4-1), 15 kA at 440 V, and 6 kA at 500 V. At 400 V it's suitable for most industrial distribution panels without upstream current-limiting fuses."},{"question":"What control voltage does the coil need?","answer":"The control circuit is 380/400 V AC 50/60 Hz — line voltage, same as the motor supply. No separate control transformer is required for the reversing contactor coil."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME14K2Q7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME14K2Q7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}