{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME16K1U7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME16K1U7","canonicalUrl":"https://aoctrl.com/schneider/GV2ME16K1U7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME16K1U7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME16K1U7, 9...14 A thermal protection, 230...240 V AC control, 3-pole.","salesMarkdown":"The Schneider Electric GV2ME16K1U7 is a direct-on-line (DOL) combination motor starter from the TeSys GV2-ME range. It integrates a 3-pole motor circuit breaker and a contactor into one unit, with a thermal protection adjustment range of 9...14 A and a 230/240 V AC control circuit at 50/60 Hz. Rated for AC-3 utilisation category, it handles motor loads up to 5.5 kW at 400/415 V AC and 7.5 kW at 500 V AC. The magnetic tripping current is set at 170 A, providing short-circuit protection that coordinates with the contactor for Type 1 coordination. ## Breaking capacity and fault protection The GV2ME16K1U7 offers a breaking capacity of 15 kA at 400/415 V AC, 8 kA at 440 V AC, and 6 kA at 500 V AC, all conforming to IEC 60947-4-1. The compact 45 mm width saves rail space compared to separate breaker-plus-contactor builds, and the fixed depth of 87 mm helps with enclosure depth planning.","metaTitle":"Schneider GV2ME16K1U7 TeSys DOL Starter, 9-14 A, 230-240 VAC","metaDescription":"Active-production DOL combination starter, 9-14 A thermal range, 5.5 kW at 400V, 15 kA breaking capacity. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"87 mm","Range":"TeSys","Width":"45 mm","title":"GV2ME16K1U7","Height":"152 mm","description":"DOL combination starter - TeSys GV2-ME - 9...14 A - 230...240 V AC","Motor power kW":"5.5 kW at 400/415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Breaking capacity":"15 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 8 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1","Coordination type":"Type 1","Device short name":"GV2ME","Poles description":"3P","Device composition":"1 3-pole contactor 1 combination block GV2AF01 1 motor circuit breaker type GV2ME","Motor starter type":"Non reversing","Utilisation category":"AC-3","Magnetic tripping current":"170 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"230/240 V AC 50/60 Hz","Thermal Protection Adjustment Range":"9...14 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d2417716df589522ebad99443cdd08c3.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV2ME16K1U7/dol-combination-starter-tesys-gv2me-9-14-a-230-240-v-ac/"},"ai":{"faq":[{"question":"What is the thermal protection range and what does it mean for motor sizing?","answer":"The thermal protection adjustment range is 9...14 A. For a 400 V three-phase motor, this covers typical induction motors rated around 5.5 kW (full-load current roughly 11-12 A). Set the dial to match the motor nameplate FLA for overload protection."},{"question":"What is the control circuit voltage requirement?","answer":"The control circuit (coil) is rated for 230/240 V AC at 50/60 Hz. Ensure your control transformer or supply matches this voltage — it is not a dual-voltage coil that also works at 110 V."},{"question":"What breaking capacity does it offer at common industrial voltages?","answer":"At 400/415 V AC it breaks 15 kA; at 440 V AC it breaks 8 kA; at 500 V AC it breaks 6 kA — all per IEC 60947-4-1. This is the maximum prospective fault current the starter can safely interrupt at those voltages."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME16K1U7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME16K1U7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}