{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME16K2Q7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME16K2Q7","canonicalUrl":"https://aoctrl.com/schneider/GV2ME16K2Q7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME16K2Q7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2ME reversing motor starter, GV2ME16K2Q7, 9...14 A thermal protection, 380/400 V AC coil, 5.5 kW at 400 V, 15 kA breaking capacity.","salesMarkdown":"The Schneider GV2ME16K2Q7 is a TeSys GV2ME reversing DOL motor starter, combining a 3-pole reversing contactor, a GV2AF01 combination block, and a GV2ME motor circuit breaker in one unit. It's designed for AC-3 motor switching duty, with a thermal protection adjustment range of 9...14 A and a magnetic trip set at 170 A. Rated motor power reaches 5.5 kW at 400/415 V AC and 7.5 kW at 500 V AC, making it a direct fit for small-to-medium three-phase induction motors on pumps, conveyors, or compressors. This starter carries a 15 kA breaking capacity at 400/415 V AC per IEC 60947-4-1, dropping to 8 kA at 440 V and 6 kA at 500 V. It's rated for Type 1 coordination, meaning after a fault the starter may need replacement but the upstream protection stays intact. ## Panel integration Depth is 87 mm, which clears most standard enclosure depths.","metaTitle":"Schneider GV2ME16K2Q7 TeSys Reversing Starter, 9-14 A, 5.5 k","metaDescription":"Active Schneider GV2ME16K2Q7 TeSys reversing motor starter, 9-14 A thermal range, 5.5 kW at 400V, 15 kA breaking capacity. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"87 mm","Range":"TeSys","Width":"45 mm","title":"GV2ME16K2Q7","Height":"152 mm","description":"DOL reversing combination starter - TeSys GV2-ME - 9...14 A - 380...400V AC","Motor power kW":"5.5 kW at 400/415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Breaking capacity":"15 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 8 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1","Coordination type":"Type 1","Device short name":"GV2ME","Poles description":"3P","Device composition":"1 3-pole reversing contactor 1 combination block GV2AF01 1 motor circuit breaker type GV2ME","Motor starter type":"Reversing","Utilisation category":"AC-3","Magnetic tripping current":"170 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"380/400 V AC 50/60 Hz","Thermal Protection Adjustment Range":"9...14 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e50a60b2866c64f5cdc0f162c5463569.pdf","sourceUrl":"https://www.se.com/in/en/product/GV2ME16K2Q7/dol-reversing-combination-starter-tesys-gv2me-9-14-a-380-400v-ac/"},"ai":{"faq":[{"question":"What motor power can this starter handle?","answer":"It handles 5.5 kW at 400/415 V AC and 440 V AC, and 7.5 kW at 500 V AC, all at 50/60 Hz. The thermal adjustment range is 9...14 A, so it's sized for motors drawing that full-load current."},{"question":"What is the breaking capacity at 400 V?","answer":"15 kA at 400/415 V AC per IEC 60947-4-1, with Type 1 coordination. At 440 V it drops to 8 kA, and at 500 V to 6 kA."},{"question":"What is the control circuit voltage?","answer":"The coil is rated for 380/400 V AC at 50/60 Hz, so it's a line-voltage coil — no separate control transformer required if the panel supplies that voltage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME16K2Q7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME16K2Q7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}