{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2ME16K2V7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2ME16K2V7","canonicalUrl":"https://aoctrl.com/schneider/GV2ME16K2V7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2ME16K2V7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2-ME reversing DOL combination starter, GV2ME16K2V7, 9...14 A thermal adjustment, 400 V AC control, 3-pole.","salesMarkdown":"The GV2ME16K2V7 is a reversing DOL combination starter from the Schneider Electric TeSys GV2-ME range — a single block that integrates a motor circuit breaker, a 3-pole reversing contactor, and an auxiliary contact block (GV2AF01) into one DIN-rail-mounted unit. It is rated for AC-3 motor starting duty with a thermal protection adjustment range of 9...14 A, so it directly protects and reverses a motor drawing up to 14 A full-load current. Motor power capability: 5.5 kW at 400/415 V AC, 5.5 kW at 440 V, and 7.5 kW at 500 V. On a 400 V line this starter handles a standard 5.5 kW four-pole induction motor; on 500 V it steps up to 7.5 kW. The thermal dial sets the overload trip between 9 A and 14 A, so it matches motors with FLC in that band. Breaking capacity: 15 kA at 400/415 V (IEC 60947-4-1), dropping to 8 kA at 440 V and 6 kA at 500 V. On a 400 V supply with a prospective fault current up to 15 kA, this starter clears the fault without upstream fuse or breaker intervention — Type 1 coordination means the starter may need contact replacement after a fault, but the rest of the panel stays intact. Magnetic trip threshold is fixed at 170 A — that is the instantaneous short-circuit pickup. Below that, the thermal bimetal handles overloads; above it, the magnetic trip opens the breaker in under a cycle. Product status is active (current production).","metaTitle":"Schneider Electric GV2ME16K2V7 TeSys reversing starter, 9-14","metaDescription":"Schneider Electric GV2ME16K2V7 TeSys reversing DOL combination starter. 9-14 A thermal range, AC-3 duty, 5.5 kW at 400 V, 15 kA breaking capacity. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"87 mm","Range":"TeSys","Width":"45 mm","Height":"152 mm","Motor power kW":"5.5 kW at 400/415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz","lifecycle_stage":"current","Breaking capacity":"15 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 8 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 6 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1","Coordination type":"Type 1","Device short name":"GV2ME","Poles description":"3P","Device composition":"1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole reversing contactor","Motor starter type":"Reversing","Utilisation category":"AC-3","Magnetic tripping current":"170 A","Product or component type":"Motor starter","[Uc] control circuit voltage":"400 V AC 50/60 Hz","Thermal Protection Adjustment Range":"9...14 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/GV2ME16K2V7/dol-reversing-combination-starter-tesys-gv2me-9-14-a-400v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2ME16K2V7/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to GV2ME16K2V7 in the TeSys family?","answer":"The GV2ME16K2V7 is a reversing combination starter; a non-reversing version (GV2ME16) shares the same thermal range and breaker but omits the reversing contactor block. For a reversing application, this is the direct fit — no pin-compatible drop-in exists because the reversing contactor is integral."},{"question":"What is the depth of GV2ME16K2V7?","answer":"87 mm — the dimension from the DIN rail mounting surface to the front of the enclosure."},{"question":"What range does GV2ME16K2V7 belong to?","answer":"TeSys — Schneider Electric's modular motor control and protection range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2ME16K2V7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2ME16K2V7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}