{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P01","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P01","canonicalUrl":"https://aoctrl.com/schneider/GV2P01","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P01","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2P01 motor circuit breaker, 3-pole, 0.16 A, thermal-magnetic, 100 kA breaking capacity, IP20, dark grey.","salesMarkdown":"The GV2P01 is a 3-pole motor circuit breaker from Schneider's TeSys Deca range, rated 0.16 A with a thermal-magnetic trip unit and a breaking capacity of 100 kA across voltages from 230 to 690 V AC. This lowest-current variant in the GV2P line is sized for fractional-horsepower motors — think small conveyor drives, fan motors, or pump starters in cement plant auxiliary systems where the line is down on a 0.16 A overload. Phase failure sensitivity per IEC 60947-4-1 means the breaker drops out if one phase goes missing, a real risk when vibration on a crusher feeder shakes a terminal loose. The thermal-magnetic unit gives both slow overload protection and instantaneous magnetic trip at 1.93 A, so it catches winding shorts without waiting for the bimetal to heat through. ## Lifecycle & sourcing status Compliance suite covers the major gate standards: UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC 60947-2, IEC/EN 60335-2-40 Annex JJ (heating appliance) and IEC/EN 60335-1 Clause 30.2 (glow-wire). Fire resistance passes 960 °C glow-wire per IEC 60695-2-11 – panel builders in hot environments (like a kiln control room) can trust the enclosure won't propagate flame. ## Mounting & wiring in the panel Accepts horizontal or vertical orientation. Depth is 97 mm (3.8 in), width 45 mm (1.8 in). Power circuit terminals accept 1…6 mm² solid or 1.5…6 mm² flexible without cable end, or 1…4 mm² with ferruled end. Tightening torque 1.7 N·m (15.05 lbf·in). ## Harsh environment resilience IP20 guards against finger contact and dust ingress; IK04 impact resistance handles accidental tool drops inside the panel. Mechanical durability 100,000 cycles, electrical durability 100,000 cycles at AC-3 rated current. Shock rated 30 Gn for 11 ms, vibration 5 Gn across 5…150 Hz – enough for service near a raw mill foundation.","metaTitle":"Schneider GV2P01 TeSys Deca Motor Circuit Breaker, 0.16A","metaDescription":"GV2P01 motor circuit breaker, 0.16 A thermal-magnetic, 3-pole, 100 kA breaking capacity, IP20. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"3.8 in (97 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122367","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws)","Control Type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"0.16 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"1.93 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Thermal protection adjustment range":"0.1...0.16 A IEC 60947-2","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"0.16 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$31.75","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c4f55a28605bffd8ea5eecd67c22137e.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P01/alternatives.json"},"ai":{"faq":[{"question":"What is GV2P01's listed color?","answer":"The GV2P01 is dark grey."},{"question":"What is GV2P01's depth?","answer":"The depth is 97 mm (3.8 in)."},{"question":"What compliance documentation does Schneider provide for GV2P01?","answer":"Standards include UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC 60947-2, IEC 60947-4-1, plus IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for glow-wire. RoHS/REACH statements are not listed in the standard product spec; request from Schneider distribution if required."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}