{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P02","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P02","canonicalUrl":"https://aoctrl.com/schneider/GV2P02","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P02","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca series, GV2P02, 3-pole motor circuit breaker, thermal-magnetic trip, 0.25 A rated current, 100 kA breaking capacity at 400 V AC.","salesMarkdown":"GV2P02: Schneider's TeSys GV2 motor circuit breaker. Three poles, 0.25 A line rated current, thermal-magnetic trip – the magnetic pickup is fixed at 3.08 A. Rated for motor protection per IEC 60947-4-1 with phase failure sensitivity and isolation suitability per IEC 60947-1. IP20 enclosure, dark grey housing. Screw-clamp terminals accept 1 to 6 mm² solid or 1.5–6 mm² flexible. Power dissipation is 2.5 W per pole at rated load. Compliance stack: UL 60947-4-1, CSA C22.2 No 60947-4-1, EN/IEC 60947-2 and -4-1. Also meets IEC/EN 60335-2-40 (Annex JJ) and IEC/EN 60335-1 (Clause 30.2). Fire resistance tested to 960 °C per IEC 60695-2-11.","metaTitle":"Schneider GV2P02 TeSys GV2 Motor Circuit Breaker, 0.25 A","metaDescription":"Schneider Electric TeSys GV2P02 motor circuit breaker, 3-pole thermal-magnetic, 0.25 A rated, 100 kA breaking, IP20. Active production, sourced to order. Standards: IEC/EN 60947, U","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"3.8 in (97 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122367","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws)","Control Type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.06 kW 400/415 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"0.25 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"3.08 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Thermal protection adjustment range":"0.16...0.25 A IEC 60947-2","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"0.25 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$31.75","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f54e02b5600f7568a54f71a3805617d4.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P02/alternatives.json"},"ai":{"faq":[{"question":"What are the key electrical ratings of GV2P02?","answer":"Line rated current 0.25 A, magnetic trip at 3.08 A, breaking capacity 100 kA at 400 V AC, rated insulation voltage 690 V AC. Suitable for motor loads up to 0.06 kW at 400 V."},{"question":"What standards does GV2P02 comply with?","answer":"Complies with IEC 60947-2 and -4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, plus clauses of IEC/EN 60335 for appliance applications."},{"question":"What is the mounting and enclosure rating?","answer":"Mounts on 35 mm DIN rail or direct panel with M4 screws. IP20 finger-safe enclosure, dark grey housing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}