{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P05KD09B7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P05KD09B7","canonicalUrl":"https://aoctrl.com/schneider/GV2P05KD09B7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P05KD09B7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2P05KD09B7 motor starter, 1 A rated current, 0.25 kW at 400 V, 100 kA breaking capacity, 24 V AC coil, 3-pole, DIN rail mount.","salesMarkdown":"The Schneider Electric TeSys GV2P05KD09B7 is a direct on-line motor starter combining a contactor and thermal-magnetic overload relay in a single 45 mm wide package. It is rated for 1 A line current and delivers 0.25 kW at 400/415 V AC or 0.55 kW at 690 V AC, making it suited for small motor loads like fans, pumps, and conveyors in control panels. The 24 V AC coil is standard for this variant, and the unit clips onto 35 mm symmetrical DIN rail or mounts with two M4 screws. The rotary knob provides manual on/off/reset control without opening the panel door. The 1 A line rated current is the continuous thermal rating — this governs the maximum motor full-load current the starter can carry without tripping. For a 0.25 kW motor at 400 V, this is a direct match; oversizing would lose overload protection resolution. The magnetic tripping current is set at 13 A, providing instantaneous short-circuit protection that clears fast on bolted faults while riding through normal motor inrush. Screw-clamp terminals accept 1 to 6 mm² solid or 1.5 to 6 mm² flexible wire without ferrules, or 1 to 4 mm² with ferrules. Tighten to 1.7 N·m — no special tooling needed beyond a standard screwdriver. The TeSys range is widely cross-referenced in OEM BOMs and MRO spares lists.","metaTitle":"Schneider TeSys GV2P05KD09B7 Motor Starter, 1 A, 0.25 kW","metaDescription":"Schneider TeSys GV2P05KD09B7 motor starter, 1 A line rated current, 0.25 kW at 400 V, 100 kA breaking capacity, 24 V AC coil, DIN rail mount, UL/CSA/IEC listed.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"3.8 in (97 mm)","Range":"TeSys","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122368","Standards":"NF C 63-650 VDE 0113 IEC 60947-1 VDE 0660 CSA C22.2 IEC 60947-4-1 NF C 63-120 NF C 79-130 IEC 60947-2 EN 60204 UL 508","Rated duty":"Continuous IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws)","Control Type":"Rotary knob","Motor power kW":"0.25 kW 400/415 V AC 50/60 Hz 0.55 kW 690 V AC 50/60 Hz","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"current","Direct connector":"Without","Flame retardance":"V1 conforming to UL 94","Pollution degree":"3","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Motor Power Range":"1.1...2 kW 200...240 V 3 phase 2.2...3 kW 380...440 V 3 phase 4...6 kW 380...440 V 3 phase 4...6 kW 480...500 V 3 phase","Network frequency":"50/60 Hz IEC 60947-4-1","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminals","Climatic withstand":"IACS E10","Line Rated Current":"1 A","Motor starter type":"Direct on-line contactor","Operating altitude":"6561.68 ft (2000 m)","Operating position":"Any position","Protective treatment":"TH","Utilisation category":"AC-4 AC-1 AC-3","Contact compatibility":"M2","Contactor application":"Resistive load Motor control","Electrical durability":"100000 cycles AC-3 440 V","Mechanical durability":"100000 cycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor open10 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms","Nbr. of units in pkg.":"1","Contactor coil voltage":"24 V AC standard","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"screw clamp terminals 2 0.002...0.009 in² (1...6 mm²) solid screw clamp terminals 2 0.002...0.009 in² (1.5...6 mm²) flexible without cable end screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"13 A","Product or Component Type":"Motor starter","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit Power circuit 10 MOhm for signalling circuit","Complementary/Utilisation category":"AC-3 IEC 60947-4-1 Category A IEC 60947-2","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient air temperature for storage":"-40...176 °F (-40...80 °C)","Ambient Air Temperature for Operation":"23...140 °F (-5...60 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"1 A IEC 60947-4-1","Complementary/[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/74dbe28e8a97ffe81e1a3ccf324be835.pdf","sourceUrl":"https://www.se.com/us/en/product/GV2P05KD09B7/motor-starter-kit-tesys-lc1d09b7-contactor-gv2p05-motor-starter-protector-24-vac-50-60-hz-coil-0-63-to-1a-trip/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P05KD09B7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this motor starter?","answer":"Line rated current is 1 A, motor power is 0.25 kW at 400/415 V AC, breaking capacity is 100 kA at 400/415 V AC, and the coil voltage is 24 V AC."},{"question":"What standards does this part comply with?","answer":"It is certified to UL 508, CSA C22.2, IEC 60947-4-1, IEC 60947-2, EN 60204, VDE 0660, and NF C 63-650 among others."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P05KD09B7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P05KD09B7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}