{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P06KD09BL","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P06KD09BL","canonicalUrl":"https://aoctrl.com/schneider/GV2P06KD09BL","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P06KD09BL","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2P06KD09BL motor starter, 1.6 A rated current, 100 kA breaking capacity, 24 V DC coil, DIN-rail mount.","salesMarkdown":"It integrates a contactor and thermal-magnetic overload relay in a single 45 mm wide package that clips onto 35 mm symmetrical DIN rail or panels with two M4 screws. Rated for continuous duty per IEC 60947-4-1, it handles motor loads from 0.37 kW at 400 V up to 0.75 kW at 690 V, and covers a motor power range of 1.1 to 2 kW on 200–240 V three-phase supply. ## Breaking capacity and protection The magnetic tripping current is set at 22.5 A, providing short-circuit protection coordinated with the contactor. Breaking capacity reaches 100 kA Icu across all common voltage levels (230/240 V, 400/415 V, 440 V, 500 V, and 690 V AC) per IEC 60947-2 — meaning it can safely interrupt fault currents up to that level without cascading upstream. Certified to IEC 60947-2, IEC 60947-4-1, UL 508, CSA C22.2, VDE 0660, and EN 60204, among others. Flame retardance is V1 per UL 94, with fire resistance tested to 1562 °F (850 °C) per IEC 60695-2-1. Pollution degree 3 rated, suitable for industrial environments. Fixes onto 35 mm symmetrical DIN rail or panel with two M4 screws. Screw-clamp terminals accept 1 to 6 mm² solid or flexible wire, with a tightening torque of 15.05 lbf·in (1.7 N·m). IP20 finger-safe protection, IK04 impact resistance.","metaTitle":"Schneider TeSys GV2P06KD09BL Motor Starter, 1.6 A, 100 kA","metaDescription":"Schneider TeSys GV2P06KD09BL motor starter, 1.6 A rated current, 100 kA breaking capacity at 400 V. Active production, DIN-rail mount. UL/CSA/IEC certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"3.8 in (97 mm)","Range":"TeSys","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122368","Standards":"IEC 60947-2 IEC 60947-4-1 VDE 0660 UL 508 NF C 79-130 CSA C22.2 VDE 0113 NF C 63-120 EN 60204 IEC 60947-1 NF C 63-650","Rated duty":"Continuous IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws)","Control Type":"Rotary knob","Motor power kW":"0.37 kW 400/415 V AC 50/60 Hz 0.37 kW 500 V AC 50/60 Hz 0.75 kW 690 V AC 50/60 Hz 0.55 kW 400/415 V AC 50/60 Hz 0.55 kW 500 V AC 50/60 Hz","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"current","Direct connector":"Without","Flame retardance":"V1 conforming to UL 94","Pollution degree":"3","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Motor Power Range":"1.1...2 kW 200...240 V 3 phase 2.2...3 kW 380...440 V 3 phase 4...6 kW 380...440 V 3 phase 4...6 kW 480...500 V 3 phase","Network frequency":"50/60 Hz IEC 60947-4-1","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminals","Climatic withstand":"IACS E10","Line Rated Current":"1.6 A","Motor starter type":"Direct on-line contactor","Operating altitude":"6561.68 ft (2000 m)","Operating position":"Any position","Protective treatment":"TH","Utilisation category":"AC-3 AC-1 AC-4","Contact compatibility":"M5","Contactor application":"Resistive load Motor control","Electrical durability":"100000 cycles AC-3 440 V","Mechanical durability":"100000 cycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor open10 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms","Nbr. of units in pkg.":"1","Contactor coil voltage":"24 V DC low consumption","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"screw clamp terminals 2 0.002...0.009 in² (1...6 mm²) solid screw clamp terminals 2 0.002...0.009 in² (1.5...6 mm²) flexible without cable end screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"22.5 A","Product or Component Type":"Motor starter","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit Power circuit 10 MOhm for signalling circuit","Complementary/Utilisation category":"AC-3 IEC 60947-4-1 Category A IEC 60947-2","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient air temperature for storage":"-40...176 °F (-40...80 °C)","Ambient Air Temperature for Operation":"23...140 °F (-5...60 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"1.6 A IEC 60947-4-1","Complementary/[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/98e902d3c0fccbb8bcc8569868dd9ed1.pdf","sourceUrl":"https://www.se.com/us/en/product/GV2P06KD09BL/motor-starter-kit-tesys-deca-lc1d09bl-contactor-gv2p06-motor-starter-protector-24-vdc-coil-1-to-1-6a-trip/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P06KD09BL/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to GV2P06KD09BL in the TeSys family?","answer":"Within the TeSys range, the primary difference between GV2P motor starters is the rated current and magnetic trip setting. The GV2P06KD09BL is set for 1.6 A with a 22.5 A magnetic trip; a sibling with a different current rating (e.g., 2.5 A or 4 A) would serve a larger motor but share the same physical footprint and DIN-rail mounting."},{"question":"What compliance documentation does Schneider provide for GV2P06KD09BL?","answer":"The starter carries certifications to IEC 60947-2, IEC 60947-4-1, UL 508, CSA C22.2, VDE 0660, and EN 60204. Flame retardance is V1 per UL 94. Schneider typically provides a Declaration of Conformity and UL/CSA file numbers upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P06KD09BL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P06KD09BL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}