{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P06TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P06TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2P06TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P06TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2P06TQ, motor circuit breaker, 3-pole, 1.6 A rated current, thermal-magnetic trip, 100 kA breaking capacity at 400 V AC, IP20.","salesMarkdown":"It's part of the GV2P family, a workhorse line for motor branch circuits up to 690 V AC. For motor protection, you'd pair this with a motor drawing up to about 0.37 kW at 400/415 V or 0.55 kW at 500 V, depending on your line voltage. The thermal-magnetic trip gives you two layers: a thermal bimetallic strip for slow overloads, and a magnetic coil set at 26.2 A for instantaneous short-circuit protection. That's a massive fault-current rating for a device this size. On a typical 480 V industrial service with a transformer feeding a motor control center, that 100 kA gives you plenty of headroom for selectivity with upstream devices. ## Where you'd use it This is a DIN-rail mount device — clips onto standard 35 mm symmetrical rail, or you can screw-mount it to a panel with two M4 screws. Mount it horizontal or vertical, doesn't matter. The rotary handle gives you manual on/off control and a clear visual position indicator. Terminal blocks accept up to 6 mm² solid or 4 mm² flexible with ferrules, torqued to 1.7 N·m. The IK04 impact rating means it can take a knock during installation without cracking the housing. The phase-failure sensitivity is a nice touch for motor protection — if you lose a phase upstream, the breaker trips rather than letting the motor single-phase and burn out. ## Standards and compliance — what the approvals mean This part carries the full suite of approvals you'd expect for a global motor-protection device: EN/IEC 60947-2 (circuit breakers), EN/IEC 60947-4-1 (contactors and motor-starters), UL 60947-4-1, and CSA C22.2 No 60947-4-1. It also meets the glow-wire test at 960 °C per IEC 60695-2-11 and the fire-resistance requirements of IEC/EN 60335 for household-appliance circuits. That UL/CSA listing means it's accepted in North American panels without extra paperwork. ## Sourcing and fit check The TeSys Deca range covers a spread of current ratings from about 0.1 A up to 32 A in the GV2P family. If your motor draws something other than 1.6 A, you'd pick a different GV2P order code with the matching In rating — same footprint, same accessories, same 100 kA breaking capacity across the range.","metaTitle":"Schneider GV2P06TQ TeSys Deca Motor Circuit Breaker, 1.6 A,","metaDescription":"Schneider Electric GV2P06TQ TeSys Deca motor circuit breaker, 1.6 A rated current, 100 kA breaking capacity at 400 V. UL/CSA/IEC compliant. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"97 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with 2 x M4 screws)","Control type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 24","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"1.6 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"26.2 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"1...1.6 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"1.6 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a372caee5456010564a7ef88239ecd29.pdf","sourceUrl":"https://www.se.com/be/en/product/GV2P06TQ/motor-circuit-breaker-tesys-deca-3p-11-6-a-thermal-magneticc-screw-clamp-terminals-tq-24-units/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P06TQ/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to know for fit?","answer":"Rated current In is 1.6 A. Breaking capacity Icu is 100 kA at 400/415 V AC. Motor power ratings: 0.37 kW at 400/415 V, 0.55 kW at 500 V, 0.75 kW at 690 V. Thermal-magnetic trip with magnetic pickup at 26.2 A."},{"question":"What compliance documentation does this part carry?","answer":"It's certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Also meets IEC/EN 60335 fire-resistance requirements and glow-wire test at 960 °C."},{"question":"What's the mounting and wiring requirement?","answer":"Mounts on 35 mm DIN rail or panel-mount with two M4 screws. Power terminals accept 1–6 mm² solid or 1.5–6 mm² flexible wire. Tightening torque is 1.7 N·m."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P06TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P06TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}