{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P07TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P07TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2P07TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P07TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2 motor circuit breaker, GV2P07TQ, 3-pole, 2.5 A rated current, thermal-magnetic trip, 100 kA breaking capacity at 400 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric TeSys GV2 GV2P07TQ is a 3-pole motor circuit breaker with a thermal-magnetic trip unit rated at 2.5 A. It's sized for a 0.75 kW motor at 400/415 V AC, 50/60 Hz, and steps up to 1.1 kW at 500 V or 1.5 kW at 690 V. The magnetic trip is fixed at 39 A, so it clears short-circuits fast without nuisance tripping on normal motor start inrush. Breaking capacity hits 100 kA Icu at 230–500 V AC per IEC 60947-2, dropping to 8 kA at 690 V. The 45 mm wide footprint (3-module) fits standard enclosure cutouts. Orientation is flexible — horizontal or vertical — so you can lay out a dense motor control center without worrying about derating for position. Power connections are screw-clamp terminals accepting up to 2 x 6 mm² solid or 2 x 4 mm² flexible with ferrule. Tightening torque is 1.7 N·m. The IP20 finger-safe front and IK04 impact rating mean it's fine inside a locked panel but not for open-machine mounting. Carries EN/IEC 60947-2 and -4-1, plus UL 60947-4-1 and CSA C22.2 No 60947-4-1 — so it's accepted in North American and European panels. Also meets IEC/EN 60335-2-40 Annex JJ for heat-pump applications and IEC/EN 60335-1 Clause 30.2 for glow-wire resistance. Fire resistance tested to 960 °C per IEC 60695-2-11.","metaTitle":"Schneider TeSys GV2 GV2P07TQ Motor Circuit Breaker, 2.5 A, 1","metaDescription":"Schneider Electric TeSys GV2 GV2P07TQ motor circuit breaker, 2.5 A rated current, 100 kA breaking capacity at 400 V. Thermal-magnetic protection, 3-pole, DIN rail mount. Active lif","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"97 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with 2 x M4 screws)","Control type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.75 kW at 400/415 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz 1.5 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 24","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"2.5 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"39 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"1...1.6 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"2.5 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c12ca44a3244a831e177000b4f135c88.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV2P07TQ/motor-circuit-breaker-tesys-deca-3p-1-62-5-a-thermal-magneticc-screw-clamp-terminals-tq-24-units/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P07TQ/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to GV2P07TQ in the same family?","answer":"Within the TeSys GV2 range, the GV2P07 (without the 'TQ' suffix) is the standard individual-pack variant. The GV2P07TQ ships as a set of 24 units on a tray, which is the only functional difference — ratings and footprint are identical."},{"question":"What are the key ratings for this motor circuit breaker?","answer":"Rated current In is 2.5 A with a fixed magnetic trip at 39 A. Breaking capacity is 100 kA Icu at 400/415 V AC. Motor power is 0.75 kW at 400 V, 1.1 kW at 500 V, 1.5 kW at 690 V. It's a 3-pole thermal-magnetic design for AC-3 and AC-3e duty."},{"question":"What compliance documentation does Schneider provide for GV2P07TQ?","answer":"The part is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. It also meets IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for appliance applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P07TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P07TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}