{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P08KD09G7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P08KD09G7","canonicalUrl":"https://aoctrl.com/schneider/GV2P08KD09G7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P08KD09G7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2P08KD09G7, motor starter, 3-pole, 4 A rated current, 100 kA breaking capacity at 400 V AC, IP20, DIN rail mount.","salesMarkdown":"## Motor starter with integrated protection The Schneider Electric TeSys GV2P08KD09G7 is a direct on-line motor starter combining a contactor and thermal-magnetic overload relay in a single 45 mm wide enclosure. Rated at 4 A line current, it covers motor power up to 1.1 kW at 400 V AC and 2.2 kW at 690 V AC. The magnetic trip threshold is set at 51 A, providing short-circuit protection coordinated with the contactor. Breaking capacity reaches 100 kA Icu at 230/240 V, 400/415 V, 440 V, and 500 V AC per IEC 60947-2, dropping to 8 kA at 690 V AC. The IP20 finger-safe enclosure suits installation inside control cabinets where personnel access is restricted. Operating position is unrestricted, and the unit withstands vibration up to 4 Gn when closed and shock up to 15 Gn for 11 ms. Screw-clamp terminals accept 1 to 6 mm² solid or stranded wire; tightening torque is 1.7 N·m. ## Duty and durability Rated for continuous duty per IEC 60947-4-1. Electrical durability is 100,000 cycles in AC-3 at 440 V; mechanical durability matches at 100,000 cycles. Maximum operating rate is 25 cycles per hour. Power dissipation per pole is 2.5 W — factor into cabinet thermal calculations when grouping multiple starters.","metaTitle":"Schneider TeSys GV2P08KD09G7 Motor Starter, 4 A, 100 kA Brea","metaDescription":"Schneider Electric TeSys GV2P08KD09G7 motor starter, 4 A rated current, 100 kA breaking capacity at 400 V. Active production. UL/CSA/IEC certified. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"3.8 in (97 mm)","Range":"TeSys","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122368","Standards":"VDE 0660 CSA C22.2 VDE 0113 EN 60204 NF C 63-650 NF C 79-130 NF C 63-120 IEC 60947-4-1 IEC 60947-1 UL 508 IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws)","Control Type":"Rotary knob","Motor power kW":"1.1 kW 400/415 V AC 50/60 Hz 1.5 kW 500 V AC 50/60 Hz 2.2 kW 690 V AC 50/60 Hz","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"current","Direct connector":"Without","Flame retardance":"V1 conforming to UL 94","Pollution degree":"3","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 8 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Motor Power Range":"0...0.5 kW 100...120 V 3 phase 0.55...1 kW 100...120 V 3 phase 0...0.5 kW 200...240 V 3 phase 0.55...1 kW 200...240 V 3 phase 1.1...2 kW 200...240 V 3 phase 0...0.5 kW 380...440 V 3 phase 0.55...1 kW 380...440 V 3 phase 1.1...2 kW 380...440 V 3 phase 2.2...3 kW 380...440 V 3 phase 4...6 kW 380...440 V 3 phase 0...0.5 kW 480...500 V 3 phase 0.55...1 kW 480...500 V 3 phase 1.1...2 kW 480...500 V 3 phase 2.2...3 kW 480...500 V 3 phase 4...6 kW 480...500 V 3 phase 0...0.5 kW 525...690 V 3 phase 0.55...1 kW 525...690 V 3 phase 1.1...2 kW 525...690 V 3 phase 2.2...3 kW 525...690 V 3 phase 4...6 kW 525...690 V 3 phase","Network frequency":"50/60 Hz IEC 60947-4-1","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminals","Climatic withstand":"IACS E10","Line Rated Current":"4 A","Motor starter type":"Direct on-line contactor","Operating altitude":"6561.68 ft (2000 m)","Operating position":"Any position","Protective treatment":"TH","Utilisation category":"AC-3 AC-1 AC-4","Contact compatibility":"M2","Contactor application":"Resistive load Motor control","Electrical durability":"100000 cycles AC-3 440 V","Mechanical durability":"100000 cycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor open10 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"screw clamp terminals 2 0.002...0.009 in² (1...6 mm²) solid screw clamp terminals 2 0.002...0.009 in² (1.5...6 mm²) flexible without cable end screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"51 A","Product or Component Type":"Motor starter","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit Power circuit 10 MOhm for signalling circuit","Complementary/Utilisation category":"AC-3 IEC 60947-4-1 Category A IEC 60947-2","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient air temperature for storage":"-40...176 °F (-40...80 °C)","Ambient Air Temperature for Operation":"23...140 °F (-5...60 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"4 A IEC 60947-4-1","Complementary/[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/015a2c9e5b690ff413830712e9c63729.pdf","sourceUrl":"https://www.se.com/us/en/product/GV2P08KD09G7/motor-starter-kit-tesys-lc1d09g7-contactor-gv2p08-motor-starter-protector-120-vac-50-60-hz-coil-2-5-to-4-0a-trip/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P08KD09G7/alternatives.json"},"ai":{"faq":[{"question":"What breaking capacity does this motor starter provide?","answer":"It provides 100 kA Icu at 230/240 V, 400/415 V, 440 V, and 500 V AC per IEC 60947-2. At 690 V AC the breaking capacity is 8 kA Icu."},{"question":"What motor power range does the GV2P08KD09G7 cover?","answer":"At 400/415 V AC it covers 0 to 1.1 kW; at 500 V AC up to 1.5 kW; at 690 V AC up to 2.2 kW. The full power range table spans 0 to 6 kW depending on voltage."},{"question":"What standards does this motor starter comply with?","answer":"It complies with IEC 60947-4-1, IEC 60947-2, UL 508, CSA C22.2, VDE 0660, EN 60204, and NF C 63-120 among others."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P08KD09G7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P08KD09G7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}