{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P10AE11TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P10AE11TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2P10AE11TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P10AE11TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2P10AE11TQ motor circuit breaker, 3-pole, thermal-magnetic, 6.3 A rated current, 100 kA breaking capacity at 400 V AC.","salesMarkdown":"The Schneider GV2P10AE11TQ is a TeSys GV2 motor circuit breaker — a 3-pole thermal-magnetic device rated at 6.3 A continuous current, designed to protect motor circuits against overloads and short circuits. It's part of the TeSys Deca range, which is the current-generation platform for motor control and protection. Motor power ratings are 2.2 kW at 400/415 V, 3 kW at 500 V, and 4 kW at 690 V, all at 50/60 Hz. The magnetic trip threshold is set at 91 A — roughly 14.4 times the rated current — which keeps it from nuisance-tripping on motor inrush while still clearing a bolted fault quickly. It fits in any standard control enclosure — horizontal or vertical orientation is fine. The rotary handle gives a clear visual indication of contact position, which helps during lockout/tagout procedures. IP20 finger-safe protection means it's suitable for enclosed panels where operators won't contact live parts. The IK04 impact rating handles the usual bumps during panel assembly. Certified to EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (contactor + motor-starter standard), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1 for North American installations. Also listed for use in appliance circuits per IEC/EN 60335-2-40 and IEC/EN 60335-1 Clause 30.2 — relevant if this goes into HVAC or refrigeration equipment. ## Sourcing and procurement takeaway This is a standard, active-production line item from the TeSys Deca family. It's specified into BOMs across panel shops and OEMs globally.","metaTitle":"Schneider GV2P10AE11TQ TeSys GV2 Motor Circuit Breaker, 6.3","metaDescription":"Schneider GV2P10AE11TQ TeSys GV2 motor circuit breaker, 6.3 A rated current, 100 kA breaking capacity at 400 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"97 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with 2 x M4 screws)","Control type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"2.2 kW at 400/415 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz 4 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 24","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"6.3 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"91 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","Auxiliary contact composition":"1 NO + 1 NC front","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"4...6.3 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"6.3 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3870283475037dfd6592c5698cfc8c24.pdf","sourceUrl":"https://www.se.com/vn/en/product/GV2P10AE11TQ/motor-circuit-breaker-tesys-deca-3p-46-3-a-thermal-magnetic-screw-clamp-terminals-with-gvae11-tq-24-units/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P10AE11TQ/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this motor circuit breaker?","answer":"Rated current 6.3 A, breaking capacity 100 kA Icu at 400/415 V AC, motor power 2.2 kW at 400 V. Magnetic trip at 91 A. Thermal-magnetic trip unit with phase-failure sensitivity."},{"question":"What standards does this part comply with?","answer":"Certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-2-40 Annex JJ. Suitable for isolation per IEC 60947-1."},{"question":"How does this mount in a panel?","answer":"Snaps onto 35 mm symmetrical DIN rail or mounts with two M4 screws. Accepts horizontal or vertical orientation. Power connections use screw clamp terminals accepting 1 to 6 mm² solid or 1.5 to 6 mm² flexible wire."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P10AE11TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P10AE11TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}