{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P10TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P10TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2P10TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P10TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2P10TQ motor circuit breaker, 3-pole, 6.3 A rated current, thermal-magnetic trip, 100 kA breaking capacity at 400 V AC, DIN-rail or panel mount.","salesMarkdown":"The headline number here is the breaking capacity: 100 kA Icu at 400/415 V AC. Motor power ratings are 2.2 kW at 400/415 V, 3 kW at 500 V, and 4 kW at 690 V — all at 50/60 Hz. The 45×89×97 mm footprint is standard for the TeSys Deca family, so swapping into an existing GV2 cutout is a direct mechanical fit. Power connections accept up to 6 mm² solid or 4 mm² flexible with ferrules; torque the screw clamps to 1.7 N·m. IP20 finger-safe terminals and IK04 impact resistance mean it's protected against accidental contact and light mechanical shock inside a closed panel. Not rated for washdown environments — this is a dry-side component. Certifications cover the major industrial markets: EN/IEC 60947-2 and -4-1 for Europe, UL 60947-4-1 for North America, CSA C22.2 No 60947-4-1 for Canada. Also listed for IEC/EN 60335 appliance standards if your machine ends up in a white-goods or HVAC line. These approvals are on the nameplate — no separate documentation chase. The 6.3 A thermal setting protects a motor drawing roughly 2.2 kW at 400 V — typical for a small conveyor, pump, or fan. The thermal-magnetic curve is fixed (no interchangeable trip blocks), so you pick the exact GV2P variant by motor FLA. Phase failure sensitivity is built in per IEC 60947-4-1, meaning it trips on single-phasing without an external relay. Electrical durability is 100,000 cycles at rated current in AC-3 duty — that's switching motor loads on and off, not just resistive loads. Mechanical durability matches at 100,000 cycles. For a motor starter that cycles several times per shift, that's years of service before contact wear becomes a concern. Power dissipation per pole is 2.5 W, so total heat in the enclosure is about 7.5 W at full load. In a dense panel with multiple breakers, that matters for thermal derating — keep ambient below 40 °C for full rated current.","metaTitle":"Schneider TeSys GV2P10TQ Motor Circuit Breaker, 6.3 A, 100 k","metaDescription":"Schneider Electric TeSys GV2P10TQ motor circuit breaker, 6.3 A rated current, 100 kA breaking capacity at 400 V. Thermal-magnetic trip, phase failure protection. Current production","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"97 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with 2 x M4 screws)","Control type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"2.2 kW at 400/415 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz 4 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 24","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"6.3 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"91 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"4...6.3 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"6.3 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9c57e09e41fee71ac02346e7ff4f582a.pdf","sourceUrl":"https://www.se.com/ie/en/product/GV2P10TQ/motor-circuit-breaker-tesys-deca-3p-46-3-a-thermal-magneticc-screw-clamp-terminals-tq-24-units/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P10TQ/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to the GV2P10TQ in the same family?","answer":"Within the TeSys Deca GV2P range, the closest sibling is the GV2P08 (rated 4 A) and GV2P14 (rated 10 A). All share the same 45 mm footprint, DIN-rail mounting, and thermal-magnetic trip design. The deciding factor is motor FLA — pick the variant whose In matches your motor nameplate."},{"question":"What compliance documentation does Schneider provide for the GV2P10TQ?","answer":"The GV2P10TQ carries EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1 certifications. It also meets IEC/EN 60335-2-40 and IEC/EN 60335-1 Clause 30.2 for appliance applications. These are listed on the product nameplate and in the manufacturer's declaration of conformity."},{"question":"What is the GV2P10TQ's depth?","answer":"The depth is 97 mm, with a width of 45 mm and height of 89 mm. This matches the standard TeSys Deca GV2P footprint for direct mechanical replacement in existing panel layouts."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P10TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P10TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}