{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P14AE11TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P14AE11TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2P14AE11TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P14AE11TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2 motor circuit breaker, GV2P14AE11TQ, 10 A rated current, thermal-magnetic trip, 3-pole, 1 NO + 1 NC auxiliary contacts, IP20, DIN rail mount.","salesMarkdown":"The Schneider Electric GV2P14AE11TQ is a TeSys GV2 motor circuit breaker rated at 10 A with a thermal-magnetic trip unit, designed for protecting 3-phase AC motor circuits up to 3 kW at 400/415 V. ## Breaking capacity and fault handling Breaking capacity hits 100 kA Icu at 230/240 V and 400/415 V AC, which means this breaker can safely interrupt a 100 kA fault current at those voltages without welding contacts or rupturing the case. That's high enough for most industrial panel bus faults—you won't need a current-limiting fuse upstream for typical installations. IP20 finger-safe protection means it's fine inside an enclosed panel but not for exposed or wet locations. The rotary handle gives local on/off control with a clear visual position. Certified to EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (motor-starter standard), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1. Also listed for IEC/EN 60335 appliance standards. That covers most global panel specs—UL for North America, IEC for Europe and Asia, CSA for Canada. The suitability-for-isolation mark (per IEC 60947-1) means you can use it as a disconnecting means under load. Rated current 10 A, magnetic trip at 149 A. Motor power: 3 kW at 400/415 V, 5 kW at 500 V, 5.5 kW at 690 V. Breaking capacity 100 kA at 400 V. Electrical durability 100,000 cycles at AC-3 duty. Phase failure sensitive—it will trip on loss of one phase, protecting the motor from single-phasing.","metaTitle":"Schneider GV2P14AE11TQ TeSys GV2 Motor Circuit Breaker, 10 A","metaDescription":"Schneider Electric GV2P14AE11TQ TeSys GV2 motor circuit breaker. 10 A rated current, 3 kW at 400 V, 100 kA breaking capacity. Active production. DIN rail mount. UL/CSA/IEC certifie","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"97 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with 2 x M4 screws)","Control type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"3 kW at 400/415 V AC 50/60 Hz 5 kW at 500 V AC 50/60 Hz 5.5 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 24","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"10 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"149 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","Auxiliary contact composition":"1 NO + 1 NC front","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"6...10 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"10 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$176.69","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/GV2P14AE11TQ/motor-circuit-breakertesys-deca-frame-23p610athermal-magneticrotary-handlescrew-clamp-terminalswith-gvae11bulk-qty/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P14AE11TQ/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the GV2P14AE11TQ?","answer":"Rated current is 10 A with a magnetic trip at 149 A. Motor power is 3 kW at 400/415 V AC. Breaking capacity is 100 kA Icu at 400/415 V AC. It has 1 NO + 1 NC auxiliary contacts built in."},{"question":"What standards does the GV2P14AE11TQ comply with?","answer":"It complies with EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335 appliance standards. It is also suitable for isolation per IEC 60947-1."},{"question":"How does the GV2P14AE11TQ mount?","answer":"It mounts on a 35 mm symmetrical DIN rail (clipped on) or directly to a panel with two M4 screws. The 45 mm width fits standard comb busbar spacing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P14AE11TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P14AE11TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}