{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P16","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P16","canonicalUrl":"https://aoctrl.com/schneider/GV2P16","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P16","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2P16, 3-pole motor circuit breaker, 14 A, 100 kA breaking capacity at 400 V AC, thermal-magnetic trip.","salesMarkdown":"## Sizing and Protection Data The GV2P16 is a 3-pole motor circuit breaker in the TeSys Deca range, rated 14 A continuous uninterrupted duty per IEC 60947-4-1. The thermal-magnetic trip unit provides motor protection with phase failure sensitivity, and magnetic tripping is set at 253.4 A. Breaking capacity reaches 100 kA at 400/415 V AC under IEC 60947-2, dropping to 50 kA at 440 V and 42 kA at 500 V. This SCCR range supports high-fault panels while maintaining selectivity with upstream devices. The unit is suitable for isolation per IEC 60947-1 and carries an IP20 enclosure rating with IK04 impact resistance. Compliance documentation covers EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, plus supplementary IEC/EN standards for fire resistance and abnormal heat. Certifications are available per standard request.","metaTitle":"Schneider GV2P16 TeSys Motor Circuit Breaker, 14A","metaDescription":"GV2P16 motor circuit breaker, 3-pole, 14 A rated current, 100 kA breaking capacity at 400 V AC. Active production. Standards: IEC 60947, UL 60947.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"3.8 in (97 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122367","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws)","Control Type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"5.5 kW 400/415 V AC 50/60 Hz 7.5 kW 500 V AC 50/60 Hz 9 kW 690 V AC 50/60 Hz 11 kW 690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 42 kA Icu 500 V AC 50/60 Hz IEC 60947-2 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"14 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"253.4 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Thermal protection adjustment range":"9...14 A IEC 60947-2","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"14 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 75 % 440 V AC 50/60 Hz IEC 60947-2 75 % 500 V AC 50/60 Hz IEC 60947-2 100 % 690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$36.83","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/981690394bd158e44ebc6953b31d1765.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P16/alternatives.json"},"ai":{"faq":[{"question":"What is GV2P16's listed color?","answer":"Dark grey."},{"question":"What is GV2P16's depth?","answer":"3.8 inches (97 mm)."},{"question":"What compliance documentation does this brand provide for GV2P16?","answer":"Standards include EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335 relevant clauses."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}