{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P16AE11TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P16AE11TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2P16AE11TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P16AE11TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2P16AE11TQ motor circuit breaker, 3-pole, 14 A rated current, thermal-magnetic trip, 100 kA breaking capacity at 400 V AC.","salesMarkdown":"Rated for motor duty at 5.5 kW on a 400 V three-phase supply, it also covers 7.5 kW at 500 V and up to 11 kW at 690 V. The magnetic trip threshold sits at 253.4 A, and it includes phase-failure sensitivity per IEC 60947-4-1 — so a lost phase on the line side won't leave the motor single-phasing to destruction. For most industrial installations fed from a 500 kVA or smaller transformer, that's more than enough headroom to avoid a cascading failure. The 6 kA rating at 690 V is a reminder that high-voltage faults are harder to interrupt; if your panel runs at 690 V, coordinate upstream accordingly. The 1 NO + 1 NC auxiliary contact set on the front lets you wire a status feedback to the PLC or a remote indicator without an add-on block. Electrical durability is rated at 100,000 cycles under AC-3 duty at 415 V, which is typical for a motor-starting profile — expect the mechanical life of 100,000 cycles to be the limiting factor if you're cycling it as a disconnect. The 45 mm width (3-module footprint) fits standard enclosure cutouts. Power terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule — two conductors per terminal, which helps when daisy-chaining to a downstream contactor. Tightening torque is 1.7 N·m on the screw clamp terminals. IP20 finger-safe protection on the front, with an IK04 impact rating — adequate for enclosed panels where operators access the handle. Certified to EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (motor-starter standard), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1 for North American installations. Also listed for IEC/EN 60335-2-40 (heat pump and air conditioner) and IEC/EN 60335-1 Clause 30.2 (glow-wire test at 960 °C per IEC 60695-2-11). Climatic withstand per IACS covers marine and humid environments.","metaTitle":"Schneider GV2P16AE11TQ TeSys Deca Motor Circuit Breaker, 14","metaDescription":"Schneider Electric GV2P16AE11TQ motor circuit breaker, 14 A rated, 100 kA breaking at 400 V. TeSys Deca series, thermal-magnetic, 1 NO + 1 NC aux. Active production. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"97 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with 2 x M4 screws)","Control type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"5.5 kW at 400/415 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz 9 kW at 690 V AC 50/60 Hz 11 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 24","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"14 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"253.4 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","Auxiliary contact composition":"1 NO + 1 NC front","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"9...14 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"14 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$176.69","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/GV2P16AE11TQ/motor-circuit-breakertesys-deca-frame-23p914athermal-magneticrotary-handlescrew-clamp-terminalswith-gvae11bulk-qty/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P16AE11TQ/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to verify for fit?","answer":"The 14 A rated current (In) and the magnetic trip threshold of 253.4 A are the primary fit parameters. For motor duty, confirm the motor FLA falls within the 14 A setting range. The 100 kA breaking capacity at 400 V AC covers most industrial service entrances."},{"question":"What compliance documentation is available for this part?","answer":"The GV2P16AE11TQ carries certifications to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. It also meets IEC/EN 60335-2-40 for heat-pump applications and has a 960 °C glow-wire test rating per IEC 60695-2-11."},{"question":"What is the mounting footprint and terminal capacity?","answer":"It mounts on 35 mm DIN rail or panel with two M4 screws. Dimensions are 45 mm wide by 89 mm high by 97 mm deep. Power terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule, two conductors per terminal, at 1.7 N·m torque."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P16AE11TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P16AE11TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}