{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P20KD25B7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P20KD25B7","canonicalUrl":"https://aoctrl.com/schneider/GV2P20KD25B7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P20KD25B7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2P20KD25B7 motor starter, 3-pole, 18 A line rated, 7.5 kW at 400 V, 24 V AC coil, IP20.","salesMarkdown":"The Schneider Electric TeSys GV2P20KD25B7 is a direct on-line motor starter combining a contactor and thermal-magnetic overload relay in a single 45 mm wide package. It is rated for 18 A line current and handles motor loads up to 7.5 kW at 400/415 V AC or 15 kW at 690 V AC, making it a fit for three-phase induction motors driving pumps, conveyors, and compressors in industrial control panels. The magnetic trip is set at 223 A, providing short-circuit protection coordinated with the thermal overload curve. Breaking capacity reaches 100 kA Icu at 230/240 V and 50 kA at 400/415 V per IEC 60947-2, which means it can safely interrupt high fault currents without upstream fuses in most distribution scenarios. The unit clips onto 35 mm symmetrical DIN rail or mounts with two M4 screws — the DIN rail option keeps panel layout flexible and speeds replacement. This starter carries approvals under UL 508, IEC 60947-1, IEC 60947-2, IEC 60947-4-1, CSA C22.2, and EN 60204, covering the major North American and European industrial control standards. At 45 mm wide and 89 mm tall, the GV2P20KD25B7 occupies a single modular DIN-rail pitch, leaving room for auxiliary contact blocks or a separate control transformer on the same rail. Screw-clamp terminals accept 1 to 6 mm² solid or stranded wire, torqued to 1.7 N·m. Rated for continuous duty per IEC 60947-4-1 with an electrical durability of 100,000 cycles in AC-3 at 440 V and mechanical durability of 100,000 cycles. The maximum operating rate of 25 cycles per hour is adequate for most motor starting applications but should be checked against frequent jogging or inching duty.","metaTitle":"Schneider TeSys GV2P20KD25B7 Motor Starter, 18 A, 7.5 kW","metaDescription":"Schneider TeSys GV2P20KD25B7 motor starter, 18 A line rated, 7.5 kW at 400 V. UL 508, IEC 60947. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"3.8 in (97 mm)","Range":"TeSys","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122368","Standards":"UL 508 IEC 60947-1 IEC 60947-2 EN 60204 NF C 79-130 NF C 63-120 NF C 63-650 IEC 60947-4-1 CSA C22.2 VDE 0113 VDE 0660","Rated duty":"Continuous IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws)","Control Type":"Rotary knob","Motor power kW":"7.5 kW 400/415 V AC 50/60 Hz 9 kW 500 V AC 50/60 Hz 15 kW 690 V AC 50/60 Hz","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"current","Direct connector":"Without","Flame retardance":"V1 conforming to UL 94","Pollution degree":"3","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 4 kA Icu 690 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2","Motor Power Range":"4...6 kW 200...240 V 3 phase 7...11 kW 380...440 V 3 phase 7...11 kW 480...500 V 3 phase","Network frequency":"50/60 Hz IEC 60947-4-1","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminals","Climatic withstand":"IACS E10","Line Rated Current":"18 A","Motor starter type":"Direct on-line contactor","Operating altitude":"6561.68 ft (2000 m)","Operating position":"Any position","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-4","Contact compatibility":"M2","Contactor application":"Resistive load Motor control","Electrical durability":"100000 cycles AC-3 440 V","Mechanical durability":"100000 cycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor closed15 Gn for 11 ms Shocks contactor open8 Gn for 11 ms","Nbr. of units in pkg.":"1","Contactor coil voltage":"24 V AC standard","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"screw clamp terminals 2 0.002...0.009 in² (1...6 mm²) solid screw clamp terminals 2 0.002...0.009 in² (1.5...6 mm²) flexible without cable end screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"223 A","Product or Component Type":"Motor starter","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit Power circuit 10 MOhm for signalling circuit","Complementary/Utilisation category":"AC-3 IEC 60947-4-1 Category A IEC 60947-2","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient air temperature for storage":"-40...176 °F (-40...80 °C)","Ambient Air Temperature for Operation":"23...140 °F (-5...60 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"18 A IEC 60947-4-1","Complementary/[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 75 % 500 V AC 50/60 Hz IEC 60947-2 50 % 400/415 V AC 50/60 Hz IEC 60947-2 75 % 440 V AC 50/60 Hz IEC 60947-2","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/41e449c99db5dc8a5d130ec2266f35ab.pdf","sourceUrl":"https://www.se.com/us/en/product/GV2P20KD25B7/motor-starter-kit-tesys-lc1d25b7-contactor-gv2p20-motor-starter-protector-24-vac-50-60-hz-coil-13-to-18a-trip/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P20KD25B7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this motor starter?","answer":"The GV2P20KD25B7 is rated 18 A line current, handles motors up to 7.5 kW at 400/415 V or 15 kW at 690 V, has a magnetic trip at 223 A, and a breaking capacity of 50 kA Icu at 400/415 V per IEC 60947-2. The coil is 24 V AC."},{"question":"What compliance documentation does this part carry?","answer":"It is certified to UL 508, IEC 60947-1, IEC 60947-2, IEC 60947-4-1, CSA C22.2, EN 60204, and VDE 0660, covering North American and European industrial control standards. The enclosure is IP20 per IEC 60529."},{"question":"How is this motor starter mounted?","answer":"It clips onto 35 mm symmetrical DIN rail or can be panel-mounted with two M4 screws. The 45 mm width fits standard modular DIN-rail spacing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P20KD25B7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P20KD25B7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}