{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P20KD25G7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P20KD25G7","canonicalUrl":"https://aoctrl.com/schneider/GV2P20KD25G7","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P20KD25G7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV2P20KD25G7, motor starter, 3 poles, 18 A rated current, 7.5 kW at 400 V, 100 kA breaking capacity, DIN rail mount.","salesMarkdown":"The Schneider Electric TeSys GV2P20KD25G7 is a direct-on-line motor starter with a rotary knob control, integrating a 3-pole contactor and thermal-magnetic protection into a single 45 mm wide unit for DIN-rail or panel mounting. Rated at 18 A line current, this starter handles 7.5 kW at 400/415 V AC and up to 15 kW at 690 V AC in AC-3 duty. The magnetic trip is set at 223 A, covering motor inrush without nuisance tripping on start. Breaking capacity reaches 100 kA at 230/240 V (Icu per IEC 60947-2), dropping to 50 kA at 400/415 V and 4 kA at 690 V. Clips onto 35 mm symmetrical DIN rail or mounts directly to the panel with two M4 screws. At 45 mm wide and 89 mm tall, three of these fit in a standard 150 mm enclosure depth with room for cable entry below. Screw-clamp terminals accept 1 to 6 mm² solid or stranded wire. Tighten to 1.7 N·m — no special tooling needed for a panel builder. Rated IP20, so it's for inside the enclosure only. Pollution degree 3 means it handles conductive dust and condensation in typical industrial cabinets. Compliance is broad: UL 508, IEC 60947-1/2/4-1, CSA C22.2, EN 60204, and VDE 0660. That covers North American, European, and many Asian regulatory gates in one part number.","metaTitle":"TeSys GV2P20KD25G7 motor starter, 18 A, 7.5 kW at 400 V","metaDescription":"TeSys GV2P20KD25G7 motor starter, 18 A rated current, 7.5 kW at 400 V, 100 kA breaking capacity. Active production. UL, IEC, CSA. DIN rail mount. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"3.8 in (97 mm)","Range":"TeSys","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122368","Standards":"UL 508 IEC 60947-1 IEC 60947-2 EN 60204 NF C 79-130 NF C 63-120 NF C 63-650 IEC 60947-4-1 CSA C22.2 VDE 0113 VDE 0660","Rated duty":"Continuous IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws)","Control Type":"Rotary knob","Motor power kW":"7.5 kW 400/415 V AC 50/60 Hz 9 kW 500 V AC 50/60 Hz 15 kW 690 V AC 50/60 Hz","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"current","Direct connector":"Without","Flame retardance":"V1 conforming to UL 94","Pollution degree":"3","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 4 kA Icu 690 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2","Motor Power Range":"4...6 kW 200...240 V 3 phase 7...11 kW 380...440 V 3 phase 7...11 kW 480...500 V 3 phase 2.2...3 kW 100...120 V 3 phase 15...25 kW 525...690 V 3 phase","Network frequency":"50/60 Hz IEC 60947-4-1","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminals","Climatic withstand":"IACS E10","Line Rated Current":"18 A","Motor starter type":"Direct on-line contactor","Operating altitude":"6561.68 ft (2000 m)","Operating position":"Any position","Protective treatment":"TH","Utilisation category":"AC-3 AC-4 AC-1","Contact compatibility":"M2","Contactor application":"Motor control Resistive load","Electrical durability":"100000 cycles AC-3 440 V","Mechanical durability":"100000 cycles","Mechanical robustness":"Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor closed15 Gn for 11 ms Shocks contactor open8 Gn for 11 ms","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"screw clamp terminals 2 0.002...0.009 in² (1...6 mm²) solid screw clamp terminals 2 0.002...0.009 in² (1.5...6 mm²) flexible without cable end screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"223 A","Product or Component Type":"Motor starter","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","Power Pole Contact Composition":"3 NO","[Ue] rated operational voltage":"Power circuit Power circuit 10 MOhm for signalling circuit","Complementary/Utilisation category":"AC-3 IEC 60947-4-1 Category A IEC 60947-2","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient air temperature for storage":"-40...176 °F (-40...80 °C)","Ambient Air Temperature for Operation":"23...140 °F (-5...60 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"18 A IEC 60947-4-1","Complementary/[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 75 % 500 V AC 50/60 Hz IEC 60947-2 50 % 400/415 V AC 50/60 Hz IEC 60947-2 75 % 440 V AC 50/60 Hz IEC 60947-2","Permissible ambient air temperature around the device":"-40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e8814eadcaaa6de76ba5166368d62f58.pdf","sourceUrl":"https://www.se.com/us/en/product/GV2P20KD25G7/motor-starter-kit-tesys-lc1d25g7-contactor-gv2p20-motor-starter-protector-120-vac-50-60-hz-coil-13-to-18a-trip/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P20KD25G7/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this part carry?","answer":"It complies with UL 508, IEC 60947-1, IEC 60947-2, IEC 60947-4-1, CSA C22.2, EN 60204, and VDE 0660. Flame retardance is V1 per UL 94."},{"question":"What motor power does this starter cover?","answer":"It is rated for 7.5 kW at 400/415 V, 9 kW at 500 V, and 15 kW at 690 V, all AC-3 duty. The motor power range covers 4–6 kW at 200–240 V and 15–25 kW at 525–690 V."},{"question":"What is the breaking capacity at 400 V?","answer":"50 kA Icu at 400/415 V AC per IEC 60947-2. That is sufficient for most industrial distribution without upstream fuses."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P20KD25G7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P20KD25G7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}