{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P32","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P32","canonicalUrl":"https://aoctrl.com/schneider/GV2P32","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P32","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca, GV2P32, motor circuit breaker, 32 A, 3-pole, thermal-magnetic, 100 kA breaking capacity at 230 V.","salesMarkdown":"Rated for 15 kW at 400 V and up to 22 kW at 690 V, it covers common IEC induction motor sizes. Breaking capacity reaches 100 kA at 230 V, dropping to 50 kA at 400 V and 4 kA at 690 V — know your supply-side fault level when coordinating. Magnetic trip is fixed at 537.6 A (roughly 17x In), which clears short-circuits fast but stays out of the way during normal starts. Phase failure sensitivity is standard, and each pole dissipates 2.5 W. Terminals accept 1 to 6 mm² solid or 1.5 to 6 mm² flexible wire; tighten to 1.7 Nm. Certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Fire resistance tested to 960 °C per IEC 60695-2-11.","metaTitle":"Schneider Electric GV2P32 TeSys Deca Motor Circuit Breaker,","metaDescription":"Active production. GV2P32 3-pole thermal-magnetic motor circuit breaker, 32 A line rated, 100 kA breaking at 230 V. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Dark grey","Depth":"3.8 in (97 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122367","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws)","Control Type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"15 kW 400/415 V AC 50/60 Hz 18.5 kW 500 V AC 50/60 Hz 22 kW 690 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 4 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"32 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"537.6 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Thermal protection adjustment range":"24...32 A IEC 60947-2","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"32 A IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % 230/240 V AC 50/60 Hz IEC 60947-2 50 % 400/415 V AC 50/60 Hz IEC 60947-2 75 % 440 V AC 50/60 Hz IEC 60947-2 75 % 500 V AC 50/60 Hz IEC 60947-2 100 % 690 V AC 50/60 Hz IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$58.42","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c4f55a28605bffd8ea5eecd67c22137e.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P32/alternatives.json"},"ai":{"faq":[{"question":"What is the GV2P32's color?","answer":"Dark grey."},{"question":"What is the GV2P32's depth?","answer":"3.8 inches (97 mm)."},{"question":"What compliance documentation does the GV2P32 carry?","answer":"It is certified to EN/IEC 60947-2 and 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and meets IEC/EN 60335 requirements for fire resistance at 960 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}