{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2P32AE11TQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2P32AE11TQ","canonicalUrl":"https://aoctrl.com/schneider/GV2P32AE11TQ","factsUrl":"https://aoctrl.com/api/mcp/products/GV2P32AE11TQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2P32AE11TQ, motor circuit breaker, 3-pole, 32 A, thermal-magnetic, 15 kW at 400 V, 100 kA Icu, IP20, DIN rail.","salesMarkdown":"The GV2P32AE11TQ is a 3-pole motor circuit breaker from the TeSys Deca family, rated 32 A continuous and built for motor protection duty. The 32 A thermal-magnetic trip unit sets the full-load current threshold for a motor branch circuit — this is the number that must match the motor nameplate FLA, not a bus rating. The magnetic trip fires at 537.6 A, which is 16.8× In, so it clears short-circuit faults fast without nuisance tripping on motor inrush. The breaking capacity tells you where this breaker can be installed: 100 kA Icu at 230/240 V AC, 50 kA at 400/415 V, and 20 kA at 440 V. Motor power ratings are 15 kW at 400/415 V, 18.5 kW at 500 V, and 22 kW at 690 V, all at 50/60 Hz. The utilisation category is AC-3, which is the standard for squirrel-cage motor switching — starting, stopping, and running motors under load. Mounting position can be horizontal or vertical. The rotary handle gives a clear visual indication of the contact position — useful for lockout/tagout. Power terminals are screw clamp, accepting up to 2 cables of 1 to 6 mm² solid or 1.5 to 6 mm² flexible. Tightening torque is 1.7 N·m. IK04 impact rating covers incidental tool drops during panel work. The GV2P32AE11TQ is certified to EN/IEC 60947-2 (circuit-breakers) and EN/IEC 60947-4-1 (motor-starters), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1. It also meets IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for appliance applications. Climatic withstand conforms to IACS, and fire resistance is tested to 960 °C per IEC 60695-2-11. Operating altitude is limited to 2000 m. Mechanical robustness: 30 Gn shock for 11 ms and 5 Gn vibration at 5 to 150 Hz. ## Durability and electrical life Electrical durability is rated at 100,000 cycles for AC-3 and AC-3e duty at 415 V at rated current. Mechanical durability matches at 100,000 cycles.","metaTitle":"Schneider TeSys GV2P32AE11TQ Motor Circuit Breaker, 32 A","metaDescription":"Schneider Electric GV2P32AE11TQ TeSys GV2 motor circuit breaker, 32 A rated current, 15 kW at 400 V, thermal-magnetic trip, 100 kA breaking capacity, current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"97 mm","Range":"TeSys Deca","Width":"45 mm","Colour":"Dark grey","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with 2 x M4 screws)","Control type":"Rotary handle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"15 kW at 400/415 V AC 50/60 Hz 18.5 kW at 500 V AC 50/60 Hz 22 kW at 690 V AC 50/60 Hz","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Quantity per set":"Set of 24","Breaking capacity":"100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2P","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Tightening torque":"1.7 N.m - on screw clamp terminal","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection","Operating altitude":"<= 2000 m","[In] rated current":"32 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"537.6 A","Phase failure sensitivity":"Yes conforming to IEC 60947-4-1","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","Auxiliary contact composition":"1 NO + 1 NC front","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"24...32 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"32 A conforming to IEC 60947-2","[Ics] rated service short-circuit breaking capacity":"100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/GV2P32AE11TQ/motor-circuit-breakertesys-deca-frame-23p2432athermal-magneticrotary-handlescrew-clamp-terminalswith-gvae11bulk-qty/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2P32AE11TQ/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this motor circuit breaker?","answer":"Rated current is 32 A with a thermal-magnetic trip unit. Magnetic trip threshold is 537.6 A. Breaking capacity is 100 kA Icu at 230/240 V, 50 kA at 400/415 V, and 20 kA at 440 V. Motor power is 15 kW at 400/415 V, 18.5 kW at 500 V, and 22 kW at 690 V. It is rated for AC-3 utilisation category and includes phase failure sensitivity."},{"question":"What compliance certifications does this part carry?","answer":"It is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. It also meets IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2. The breaker is suitable for isolation per IEC 60947-1."},{"question":"What are the mounting options for the GV2P32AE11TQ?","answer":"It mounts on a 35 mm symmetrical DIN rail or directly to a panel with two M4 screws. Mounting position can be horizontal or vertical. The control is a rotary handle."},{"question":"What is the physical size of this breaker?","answer":"Depth is 97 mm, width is 45 mm, and height is 89 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2P32AE11TQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2P32AE11TQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}