{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2RT033","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2RT033","canonicalUrl":"https://aoctrl.com/schneider/GV2RT033","factsUrl":"https://aoctrl.com/api/mcp/products/GV2RT033","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca, GV2RT033, motor circuit breaker, 3P, 0.4 A, thermal-magnetic, 100 kA Icu at 400 V, 45 mm wide.","salesMarkdown":"It uses a thermal-magnetic trip unit — the thermal element handles overloads, the magnetic element handles short circuits — and is sized for the smallest fractional-horsepower motors: 0.06 kW at 230 V, 0.09 kW at 400 V, 0.12 kW at 440 V. The 100 kA rating holds across the full voltage range up to 690 V — that is unusually high for a 0.4 A breaker and means it is safe on high-SCCR installations. The electrical durability is 100,000 cycles at 415 V in AC-3, so it is not a one-shot device — it lives through repeated starts in a production line. ## How it mounts and connects At 45 mm wide it takes one standard 9 mm pitch on the rail, leaving room alongside contactors or other breakers. Spring-clamp terminals accept 1 to 6 mm² solid or 1.5 to 4 mm² flexible with ferrules — no screwdriver torque check needed, which speeds up wiring on a panel build. Mounts horizontally or vertically. The toggle control is manual, so it is a local disconnect — no remote trip coil. Thermal protection adjustment range: 0.25 to 0.4 A — you set the overload threshold within that window to match the motor full-load current. Magnetic trip fixed at 8 A, which is 20 times the rated current, so it avoids nuisance trips on inrush. Breaking capacity: 100 kA Icu at 230 V, 400 V, 440 V, 500 V, and 690 V — the full range. That is a category A breaker (no intentional short-time delay) per IEC 60947-2, so it clears faults fast without waiting for downstream devices. Power dissipation per pole: 2.5 W. Ambient operating range: -20 to 60 °C. Storage: -40 to 80 °C. IP20 finger-safe terminals, IK04 impact resistance. Climatic withstand per IACS for marine or humid environments.","metaTitle":"Schneider TeSys GV2RT033 Motor Circuit Breaker, 0.4 A, 100 k","metaDescription":"Schneider Electric GV2RT033 TeSys Deca motor circuit breaker. Rated 0.4 A, thermal-magnetic trip, 100 kA breaking capacity at 400 V. Current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"78.5 mm","Range":"TeSys Deca","Width":"45 mm","Height":"89 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Uninterrupted conforming to IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)","Control type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.06 kW at 220/230 V AC 50/60 Hz motor protection high peak current 0.09 kW at 400/415 V AC 50/60 Hz motor protection high peak current 0.09 kW at 440 V AC 50/60 Hz motor protection high peak current 0.12 kW at 440 V AC 50/60 Hz motor protection high peak current","Fire resistance":"960 °C conforming to IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"GV2RT","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz conforming to IEC 60947-2","Poles description":"3P","Climatic withstand":"conforming to IACS E10","Device application":"Motor protection Transformer","Operating altitude":"<= 2000 m","[In] rated current":"0.4 A","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1","Electrical durability":"100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz","Connections - terminals":"Power circuit: spring terminals 2 cable(s) 1...6 mm²solid Power circuit: spring terminals 2 cable(s) 1.5...4 mm²flexible without cable end Power circuit: spring terminals 2 cable(s) 1...4 mm²flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping current":"8 A","Product or component type":"Motor circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...80 °C","Thermal protection adjustment range":"0.25...0.4 A conforming to IEC 60947-2","Ambient air temperature for operation":"-20...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","[Ith] conventional free air thermal current":"0.4 A conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8a02b83a077b05d464b9f6ff6a8fa885.pdf","sourceUrl":"https://www.se.com/vn/en/product/GV2RT033/motor-circuit-breaker-tesys-deca-3p-0-250-4-a-thermal-magnetic-spring-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2RT033/alternatives.json"},"ai":{"faq":[{"question":"What is the GV2RT033's depth?","answer":"78.5 mm. That is the dimension from the DIN-rail mounting surface to the front of the toggle — important for enclosure depth clearance."},{"question":"What is the GV2RT033's range?","answer":"TeSys Deca, the Schneider Electric range of motor circuit breakers and contactors for IEC installations."},{"question":"What compliance documentation does Schneider provide for the GV2RT033?","answer":"It is certified to EN/IEC 60947-2 and EN/IEC 60947-4-1. Climatic withstand per IACS. Fire resistance at 960 °C per IEC 60695-2-11. The standard declaration of conformity covers CE, UKCA, and EAC for the TeSys Deca range."},{"question":"What is the closest alternative to the GV2RT033 in the TeSys family?","answer":"The GV2RT series shares the same 45 mm footprint and terminal layout. The deciding factor is the thermal adjustment range: the GV2RT033 covers 0.25 to 0.4 A. A sibling like the GV2RT034 covers a higher band. If your motor FLA falls within 0.25 to 0.4 A, this is the correct fit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2RT033","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2RT033 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}