{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV2RT04","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV2RT04","canonicalUrl":"https://aoctrl.com/schneider/GV2RT04","factsUrl":"https://aoctrl.com/api/mcp/products/GV2RT04","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV2RT04, motor circuit breaker, 3-pole, 0.63 A, 100 kA Icu at 400 V, thermal-magnetic.","salesMarkdown":"The Schneider Electric GV2RT04 is a 3-pole motor circuit breaker from the TeSys Deca range, rated 0.63 A and offering 100 kA interrupting capacity across 220 V to 690 V AC — that breaking capacity holds at 400 V and 690 V, so it covers installations with high available fault current without requiring an upstream fuse. The thermal-magnetic trip unit combines inverse-time overload protection with instantaneous magnetic trip set at 13 A. Sized for small motors and transformers: at 400 V it protects a 0.12 kW motor; at 690 V it covers up to 0.37 kW. Depth of 3.09 inches (78.5 mm) fits standard enclosures; the IP20 finger-safe terminals accept up to 6 mm² solid or 4 mm² flexible with ferrule.","metaTitle":"Schneider TeSys GV2RT04 Motor Circuit Breaker, 0.63 A, 100 k","metaDescription":"Schneider TeSys Deca GV2RT04 motor circuit breaker, 3-pole, rated 0.63 A with 100 kA Icu at 400 V. Thermal-magnetic trip, AC-3 duty. Active production – standard channel availabili","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"3.09 in (78.5 mm)","Range":"TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.5 in (89 mm)","Category":"US10I1122367","Standards":"EN/IEC 60947-2 EN/IEC 60947-4-1","Rated duty":"Uninterrupted IEC 60947-4-1","Fixing mode":"35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate)","Control Type":"Toggle","Network type":"AC","Product name":"TeSys GV2","Motor power kW":"0.12 kW 400/415 V AC 50/60 Hz motor protection high peak current 0.18 kW 400/415 V AC 50/60 Hz motor protection high peak current 0.18 kW 440 V AC 50/60 Hz motor protection high peak current 0.37 kW 690 V AC 50/60 Hz motor protection high peak current","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Breaking capacity":"100 kA Icu 220/230 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2","Device short name":"GV2RT","Mounting position":"Horizontal Vertical","Network frequency":"50/60 Hz IEC 60947-2","Poles description":"3P","Tightening torque":"15.05 lbf.in (1.7 N.m) screw clamp terminal","Climatic withstand":"IACS E10","Device Application":"Motor protection Transformer","Line Rated Current":"0.63 A","Operating altitude":"<= 6561.68 ft (2000 m)","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1","Electrical durability":"100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In","Mechanical durability":"100000 cycles","Mechanical robustness":"Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit screw clamp terminal 2 0.002...0.009 in² (1...6 mm²)solid Power circuit screw clamp terminal 2 0.002...0.009 in² (1.5...6 mm²)flexible without cable end Power circuit screw clamp terminal 2 0.002...0.006 in² (1...4 mm²)flexible with cable end","IK degree of protection":"IK04","IP degree of protection":"IP20 IEC 60529","Magnetic tripping current":"13 A","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"2.5 W","[Ui] rated insulation voltage":"690 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-40...176 °F (-40...80 °C)","Thermal protection adjustment range":"0.4...0.63 A IEC 60947-2","Ambient air temperature for operation":"-4...140 °F (-20...60 °C)","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947-2","[Ith] conventional free air thermal current":"0.63 A IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$162.59","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/374b4183068226eb65a40123574d7942.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV2RT04/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV2RT04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV2RT04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}